| 2022-02-17 13:07:09 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) FOR VERIFICATION PURPOSES PLEASE PROVIDE A |
| | FLOOR/SITE PLAN CLEARLY INDICATING THE PROPOSED |
| | LOCATION. |
| | |
| | |
| | 2) SHOULD THE LOCATION BE INSTALLED WITHIN THE EXISTING |
| | BUILDING, THE FIRE SPRINKLER PROTECTION SHALL BE |
| | EXTENDED INTO THE COOLER. |
| | |
| | PER NFPA 101, CH 12 |
| | |
| | 12.3.5.4 WHERE ANOTHER PROVISION OF THIS CHAPTER |
| | REQUIRES AN AUTOMATIC |
| | SPRINKLER SYSTEM, THE SPRINKLER SYSTEM SHALL BE |
| | INSTALLED IN ACCORDANCE |
| | WITH 9.7.1.1(1). |
| | |
| | 9.7 AUTOMATIC SPRINKLERS |
| | 9.7.1 GENERAL. |
| | 9.7.1.1* EACH AUTOMATIC SPRINKLER SYSTEM REQUIRED BY |
| | ANOTHER SECTION |
| | OF THIS CODE SHALL BE IN ACCORDANCE WITH ONE OF THE |
| | FOLLOWING: |
| | |
| | (1) NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER |
| | SYSTEMS |
| | (2) NFPA 13D, STANDARD FOR THE INSTALLATION OF |
| | SPRINKLER SYSTEMS IN |
| | ONE- AND TWO-FAMILY DWELLINGS AND MANUFACTURED HOMES |
| | (3) NFPA 13R, STANDARD FOR THE INSTALLATION OF |
| | SPRINKLER SYSTEMS IN |
| | LOW-RISE RESIDENTIAL OCCUPANCIES |
| | |
| | PER NFPA 13 |
| | |
| | 8.1.1* THE REQUIREMENTS FOR SPACING, LOCATION, AND |
| | POSITION OF SPRINKLERS SHALL BE BASED ON |
| | THE FOLLOWING PRINCIPLES: |
| | (1) SPRINKLERS SHALL BE INSTALLED THROUGHOUT THE |
| | PREMISES. |
| | |
| | A.8.1.1 THIS STANDARD CONTEMPLATES FULL SPRINKLER |
| | PROTECTION FOR ALL AREAS INCLUDING WALK-IN |
| | COOLERS, FREEZERS, BANK VAULTS, AND SIMILAR AREAS. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT FOR |
| | FIRE SPRINKLER WORK TO BE SUBMITTED UNDER SEPARATE |
| | PERMIT & SHOP DRAWINGS. |
| | |
| | |
| | 3) AS THIS IS A DOUBLE COMPARTMENT COOLER, IS THE PATH |
| | OF EGRESS LIGHTING PROVIDED WITH BACK UP POWER IN CASE |
| | OF LOSS OF POWER? |
| | |
| | PER NFPA 101 CH 12 |
| | |
| | 12.2.9 EMERGENCY LIGHTING. |
| | 12.2.9.1 EMERGENCY LIGHTING SHALL BE PROVIDED IN |
| | ACCORDANCE WITH SECTION 7.9. |
| | |
| | PLEASE PROVIDE FOR PATH OF EGRESS EMERGENCY LIGHTING |
| | WITHIN THE EACH COMPARTMENT OF THE COOLER. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |