2022-02-17 13:07:09THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) FOR VERIFICATION PURPOSES PLEASE PROVIDE A
 FLOOR/SITE PLAN CLEARLY INDICATING THE PROPOSED
 LOCATION.
  
  
 2) SHOULD THE LOCATION BE INSTALLED WITHIN THE EXISTING
 BUILDING, THE FIRE SPRINKLER PROTECTION SHALL BE
 EXTENDED INTO THE COOLER.
  
 PER NFPA 101, CH 12
  
 12.3.5.4 WHERE ANOTHER PROVISION OF THIS CHAPTER
 REQUIRES AN AUTOMATIC
 SPRINKLER SYSTEM, THE SPRINKLER SYSTEM SHALL BE
 INSTALLED IN ACCORDANCE
 WITH 9.7.1.1(1).
  
 9.7 AUTOMATIC SPRINKLERS
 9.7.1 GENERAL.
 9.7.1.1* EACH AUTOMATIC SPRINKLER SYSTEM REQUIRED BY
 ANOTHER SECTION
 OF THIS CODE SHALL BE IN ACCORDANCE WITH ONE OF THE
 FOLLOWING:
  
 (1) NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
 SYSTEMS
 (2) NFPA 13D, STANDARD FOR THE INSTALLATION OF
 SPRINKLER SYSTEMS IN
 ONE- AND TWO-FAMILY DWELLINGS AND MANUFACTURED HOMES
 (3) NFPA 13R, STANDARD FOR THE INSTALLATION OF
 SPRINKLER SYSTEMS IN
 LOW-RISE RESIDENTIAL OCCUPANCIES
  
 PER NFPA 13
  
 8.1.1* THE REQUIREMENTS FOR SPACING, LOCATION, AND
 POSITION OF SPRINKLERS SHALL BE BASED ON
 THE FOLLOWING PRINCIPLES:
 (1) SPRINKLERS SHALL BE INSTALLED THROUGHOUT THE
 PREMISES.
  
 A.8.1.1 THIS STANDARD CONTEMPLATES FULL SPRINKLER
 PROTECTION FOR ALL AREAS INCLUDING WALK-IN
 COOLERS, FREEZERS, BANK VAULTS, AND SIMILAR AREAS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT FOR
 FIRE SPRINKLER WORK TO BE SUBMITTED UNDER SEPARATE
 PERMIT & SHOP DRAWINGS.
  
  
 3) AS THIS IS A DOUBLE COMPARTMENT COOLER, IS THE PATH
 OF EGRESS LIGHTING PROVIDED WITH BACK UP POWER IN CASE
 OF LOSS OF POWER?
  
 PER NFPA 101 CH 12
  
 12.2.9 EMERGENCY LIGHTING.
 12.2.9.1 EMERGENCY LIGHTING SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTION 7.9.
  
 PLEASE PROVIDE FOR PATH OF EGRESS EMERGENCY LIGHTING
 WITHIN THE EACH COMPARTMENT OF THE COOLER.
  
  
  
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709