| 2022-02-15 16:08:12 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22020041 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR THIS USE OF SPACE. FBC EC C403.2.1 | | | | | | 2) PLEASE SHOW THE OUTDOOR AIR CALCULATIONS FOR THIS | | | USE OF SPACE. FBC M 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | 3) FROM THE DRAWING SUBMITTED IT IS UNCLEAR TO THIS | | | REVIEWER IF THE OUTDOOR AIR LOUVER FOR THE HP-G1.2 IS | | | TERMINATING ON THE EXTERIOR OF THE BUILDING OR IN THE | | | GARAGE. PLEASE SHOW THAT THE OUTDOOR AIR LOUVER IS ON | | | THE EXTERIOR OF THE BUILDING AND NOT IN THE GARAGE. FBC | | | 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|