Plan Review Notes
Plan Review Notes For Permit 22020036
Permit Number 22020036
Review Stop M
Sequence Number 1
Notes
Date Text
2022-02-09 10:35:52IT APPEARS THAT THE MECHANICAL WORK IS FOR A LIKE FOR
 LIKE CHANGE OUT OF THE AHU AND CONDENSING UNIT. THE
 DRAWING SUBMITTED IS UNCLEAR IF THIS IS THE CASE. THE
 RAWING HAS DUCTWORK ON THE DRAWING AS WELL AND THE
 SCOPE OF WORK FOR THE PROJECT STATES UPGRADE A/C TO
 CURRENT STANDARDS. IS THE DUCTWORK ALSO INCLUDED IN THE
 MECHANICAL SCOPE OF WORK? PLEASE ALSO SHOW THE LOCATION
 OF THE NEW CONDENSING UNIT ON THE DRAWING AND SHOW THE
 TIED DOWN METHOD THAT WILL BE USED. FBC 107.2.1
  