Plan Review Notes
Plan Review Notes For Permit 22020029
Permit Number 22020029
Review Stop P
Sequence Number 1
Notes
Date Text
2022-02-07 14:17:2102/07/22 PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING PLUMBING PERMITS WITH INSPECTIONS OF THIS
 STRUCTURE. SINCE THERE IS NO RECORD OF A PERMIT AND THE
 DRAWING AS-BUILT OF EXISTING FOR TWO-BEDROOM ONE BATH
 WAS SUBMITTED FOR APPROVAL, THE INSPECTOR MAY REQUEST
 THE CAMERA VIDEOS OF PIPES.
  
 2. THE STRUCTURE IS NOT THE SAME AS THE ONE ON PLANS
 FOR THE WORK AREA PROPOSED. DIMENSIONS OF THE BUILDING
 DO NOT MATCH THE ONES ON FILE IN THE RECORD. THEY MATCH
 THE REAR STRUCTURE. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 3. ON SHEET P-1;
  
 A. WOULD YOU PLEASE SHOW THE CLEANOUT LOCATION PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. THE ISOMETRIC HAS NO SHUT-OFF VALVE, AND EACH
 DWELLING UNIT SHALL BE PROVIDED WITH AN ACCESSIBLE MAIN
 SHUTOFF VALVE NEAR THE ENTRANCE OF THE WATER SERVICE R
 2903.9.1 SERVICE VALVE.
  
 C. THERE IS NO WASHING MACHINE, AND ONE CONNECTION PER
 DWELLING UNIT IS REQUIRED PER THE TABLE 403.1 MINIMUM
 NUMBER OF REQUIRED PLUMBING FIXTURES.
  
 4. ON SHEET P-2;
  
 A. THE TERMINATION FOR THE HEATER RELIEF DOES NOT
 COMPLY WITH THE 2020 FBC SEC. R 2804.6.1(2) DISCHARGE
 THROUGH AN AIR GAP LOCATED IN THE SAME ROOM AS THE
 WATER HEATER.
  
 B. WATER HEATER REQUIRES A DRAIN PAN PER THE 2020 FBC
 SEC. R 2801.6 REQUIRED PAN. SHOW THE TERMINATION OF THE
 PAN DRAIN TO THE EXTERIOR OF THE STRUCTURE PER THE 2020
 FBC SEC. R 2801.6.2 PAN DRAIN TERMINATION.
  
 C. WOULD YOU PLEASE SHOW THE TERMINAL EXPANSION VALVE
 THAT SHALL BE INSTALLED WHERE REQUIRED IN ACCORDANCE
 WITH SECTIONS P2903.4.1 AND P2903.4.2.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  