| 2022-03-01 17:31:18 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22020021 |
| | 3/1/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED CPOMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| | CAPS FOR CLARIFICATION. |
| | |
| | 2) FAILED. SHEET P1.0 & P1.3: SHOW THE LOCATIONS OF THE |
| | SAMPLING PORT ON P1.0, AND INCLUDE THE GREASE |
| | INTERCEPTOR AND VENT LINE IN THE RISER DRAWING- SEC. |
| | 1003.3.5 FBC P. THE MANUFACTURER RECOMMENDED SAMPLING |
| | PORT HAS HAS BEEN REMOVED. PLEASE PROVIDE DATA |
| | INDICATING THE REMAINING CLEANOUTS CAN BE USED FOR |
| | SAMPLING THE EFFLUENT. |
| | |
| | 3) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE INTERCEPTOR AND |
| | SAMPLING PORT- SEC. 1003.3.5 FBC P. PLEASE NOTE THAT |
| | SCHIER RECOMMENDS REINFORCED CONCRETE SLABS FOR BELOW |
| | GRADE INSTALLATIONS. THE SPECS SHEETS WERE SUBMITTED |
| | BUT NOT THE INSTALLATION INSTRUCTIONS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |