| Plan Review Notes For Permit 22020021 |
| Permit Number |
22020021 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-18 14:16:50 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 22020021 | | | 2/18/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SUBMIT REVISED CIVIL PLANS FOR ENGINEERING | | | REVIEW- SEC. 107.2.1 WPB. | | | | | | 2) SHEET P1.0 & P1.3: SHOW THE LOCATIONS OF THE | | | SAMPLING PORT ON P1.0, AND INCLUDE THE GREASE | | | INTERCEPTOR AND VENT LINE IN THE RISER DRAWING- SEC. | | | 1003.3.5 FBC P. | | | | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE INTERCEPTOR AND | | | SAMPLING PORT- SEC. 1003.3.5 FBC P. PLEASE NOTE THAT | | | SCHIER RECOMMENDS REINFORCED CONCRETE SLABS FOR BELOW | | | GRADE INSTALLATIONS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|