Plan Review Notes
Plan Review Notes For Permit 22020021
Permit Number 22020021
Review Stop P
Sequence Number 1
Notes
Date Text
2022-02-18 14:16:501ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22020021
 2/18/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT REVISED CIVIL PLANS FOR ENGINEERING
 REVIEW- SEC. 107.2.1 WPB.
  
 2) SHEET P1.0 & P1.3: SHOW THE LOCATIONS OF THE
 SAMPLING PORT ON P1.0, AND INCLUDE THE GREASE
 INTERCEPTOR AND VENT LINE IN THE RISER DRAWING- SEC.
 1003.3.5 FBC P.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE INTERCEPTOR AND
 SAMPLING PORT- SEC. 1003.3.5 FBC P. PLEASE NOTE THAT
 SCHIER RECOMMENDS REINFORCED CONCRETE SLABS FOR BELOW
 GRADE INSTALLATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  