| 2022-08-22 12:38:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | SOME OF THE PREVIOUS FIRE COMMENTS WERE NOT ADDRESSED. |
| | |
| | PLEASE NOTE BELOW AND RESPOND TO EACH INDIVIDUAL |
| | COMMENT SPECIFICALLY. |
| | |
| | |
| | 1) FOR CLARIFICATION AND COMFIRMATION, PLEASE PROVIDE |
| | THE APPROVED OCCUPANCY OF THIS BUILDING, IT IS AN |
| | EDUCATIONAL OR DAYCARE OCCUPANCY. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | *************** COMMENT NOT ADDRESSED************** |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 1A) THERE IS AN INDICATION OF NEW CLASSROOMS WITH |
| | OPENINGS TO A COMMON INTERIOR AREA. |
| | |
| | THERE ARE NO DIMENSIONS INDICATED FOR THE OPENINGS. |
| | |
| | ***********COMPLIED******************** |
| | |
| | |
| | |
| | ARE DOORS PROPOSED FOR THESE OPENINGS? |
| | |
| | *************** COMMENT NOT ADDRESSED************** |
| | |
| | NEW DRAWING 003 DIVIDING ROOM INDICATES "36" TYPICAL |
| | DOOR", BUT THERE IS NO DOOR SCHEDULE NOR DOOR HARDWARE. |
| | |
| | ARE THESE JUST OPENINGS OR WILL DOORS BE INSTALLED. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF SMOKE ALARMS OR FIRE |
| | ALARM DEVICES WITHIN THE NEW CLASSROOMS. |
| | |
| | THIS OCCUPANCY WAS INSTALLED WITH A FIRE ALARM |
| | PREVIOUSLY. |
| | |
| | *************** COMMENT NOT ADDRESSED************** |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT THAT FIRE |
| | ALARM/SA DEVICES WILL BE INSTALLED UNDER SEPARATE |
| | PERMIT AND SHOP DRAWINGS. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |