2022-03-01 13:29:581ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22011328
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADJUST THE PROJECT VALUE ON THE PERMIT
 APPLICATION TO REFLECT THE ACTUAL COST OF THIS PROJECT.
  
 2) PLEASE SHOW THE CLEANOUTS AT EVERY CHANGE IN
 DIRECTION FOR THE GREASE DUCT ON ALL KITCHEN HOOD DUCT.
 FBC M 506.3.9
  
 3) SHEET KH-4 INDICATES ON THE DETAIL DUCT DRAWING A
 KEF-2 BUT THE SPECS ARE FOR KEF-1. PLEASE BE
 CONSISTENT. FBC 107.2.1
  
 4) SHEET KH-9 INDICATES ON THE DETAIL DUCT DRAWING A
 KEF-1 BUT THE SPECS ARE FOR KEF-2. PLEASE BE
 CONSISTENT. FBC 107.2.1
  
 5) SHEET KH-13: PLEASE PROVIDE A DETAIL FOR THE
 DUCTWORK FOR THE DISH HOOD. FBC 107.2.1
  
 6) PLEASE SHOW THAT MUA NUMBER 1 AND MUA NUMBER 2 WILL
 MEET THE 10 FEET DISTANCE FROM THE ROOFS EDGE OR HAVE
 GUARDS. FBC M 304.11
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  