| Date |
Text |
| 2022-03-01 13:29:58 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-22011328 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE ADJUST THE PROJECT VALUE ON THE PERMIT |
| | APPLICATION TO REFLECT THE ACTUAL COST OF THIS PROJECT. |
| | |
| | 2) PLEASE SHOW THE CLEANOUTS AT EVERY CHANGE IN |
| | DIRECTION FOR THE GREASE DUCT ON ALL KITCHEN HOOD DUCT. |
| | FBC M 506.3.9 |
| | |
| | 3) SHEET KH-4 INDICATES ON THE DETAIL DUCT DRAWING A |
| | KEF-2 BUT THE SPECS ARE FOR KEF-1. PLEASE BE |
| | CONSISTENT. FBC 107.2.1 |
| | |
| | 4) SHEET KH-9 INDICATES ON THE DETAIL DUCT DRAWING A |
| | KEF-1 BUT THE SPECS ARE FOR KEF-2. PLEASE BE |
| | CONSISTENT. FBC 107.2.1 |
| | |
| | 5) SHEET KH-13: PLEASE PROVIDE A DETAIL FOR THE |
| | DUCTWORK FOR THE DISH HOOD. FBC 107.2.1 |
| | |
| | 6) PLEASE SHOW THAT MUA NUMBER 1 AND MUA NUMBER 2 WILL |
| | MEET THE 10 FEET DISTANCE FROM THE ROOFS EDGE OR HAVE |
| | GUARDS. FBC M 304.11 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |