| 2022-02-02 10:18:15 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL7849-R14 HAS BEEN REVISED TO FL7849-R15. |
| | PLEASE PROVIDE A COMPLETE SET OF PRODUCT APPROVALS. |
| | INCLUDE COVER PAGE, EVALUATION REPORTS AND INSTALLATION |
| | INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS |
| | AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| | PRODUCT APPROVAL DRAWINGS. |
| | 2. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL1654-R27 HAS BEEN REVISED TO FL1654-R28. |
| | PLEASE PROVIDE A COMPLETE SET OF PRODUCT APPROVALS. |
| | INCLUDE COVER PAGE, EVALUATION REPORTS AND INSTALLATION |
| | INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS |
| | AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| | PRODUCT APPROVAL DRAWINGS. |
| | 3. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL1654-R27 SYSTEM NO. W-209 DOES NOT MEET THE |
| | MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17 |
| | FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT |
| | MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR |
| | EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED |
| | ENGINEERED NAILING CALCULATIONS WITH AN APPROVED |
| | SYSTEM. |
| | 4. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R34 |
| | COVERS MULTIPLE PRODUCT TYPES; ROOF COVER OPTIONS; |
| | ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS & |
| | ALLOWABLE SUBSTRATES. SELECT PRODUCT TYPE, ROOF COVER |
| | OPTIONS, ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE |
| | COMBINATIONS TO BE USED. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. |
| | 5. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH AND INCLUDE ROOF SLOPE(S), MEAN ROOF |
| | HEIGHT(S). LOW SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. |
| | 6. WPB A 109.3 BUILDING PERMIT VALUATIONS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| | QUANTITY ESTIMATES. VALUE TO INCLUDE LABOR AND |
| | MATERIALS, ARCHITECTURAL AND DESIGN FEES, OVERHEAD AND |
| | PROFIT. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |