| Plan Review Notes For Permit 22011278 |
| Permit Number |
22011278 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-17 12:36:32 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22011278 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M2.01; VAV-16-12 PLEASE SHOW THE CFM?S OF | | | SUPPLY AIR AT THE GRILLES. | | | | | | 2) SHEET M2.01; VAV-16-17; THE DESIGN FLOW IS 2700 BUT | | | THE DRAWING SHOWS 2890. | | | | | | 3) SHEET M2.01; VAV-16-11; THE DESIGN FLOW IS 600 BUT | | | THE DRAWING SHOWS 700. | | | | | | 4) SHEET M2.02; VAV-16-01; THE DESIGN FLOW IS 750 BUT | | | THE DRAWING SHOWS 700. | | | | | | 5) SHEET M2.03; VAV-16-09; THE DESIGN FLOW IS 800 BUT | | | THE DRAWING SHOWS 750. | | | | | | 6) SHEET M2.09; VAV-17-10; THE DESIGN FLOW IS 1040 BUT | | | THE DRAWING SHOWS 1090. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|