2022-02-24 10:10:37OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ADDED CONVENIENCE STAIR - IS THE SLAB CUT EXISTING?
 - PLEASE SHOW THE STRUCTURAL DETAILS FOR THE SLAB CUT
 AND REPAIR.
  
 2) CONVENIENCE STAIR - PLEASE SHOW THE RISERS TO BE
 CLOSED OR LESS THAN 4" OPENING PER FBC 1011.5.5.3 SOLID
 RISERS.
 RISERS SHALL BE SOLID.
  
 EXCEPTIONS: (1) SOLID RISERS ARE NOT REQUIRED FOR
 STAIRWAYS THAT ARE NOT REQUIRED TO COMPLY WITH SECTION
 1009, PROVIDED THAT THE OPENING BETWEEN TREADS DOES NOT
 PERMIT THE PASSAGE OF A SPHERE WITH A DIAMETER OF 4
 INCHES (102 MM).
  
 3) CONVENIENCE STAIR - PLEASE PROVIDE A STATEMENT ON
 THE DRAWINGS THAT THE GLASS IN THE GUARD RAILS COMPLY
 WITH FBC 2407.1 MATERIALS.
 GLASS USED IN A HANDRAIL, GUARDRAIL OR GUARD SECTION
 SHALL BE LAMINATED GLASS CONSTRUCTED OF FULLY TEMPERED
 OR HEAT-STRENGTHENED GLASS AND SHALL COMPLY WITH
 CATEGORY II OR CPSC 16 CFR PART 1201 OR CLASS A OF ANSI
 Z97.1. GLAZING IN RAILING IN-FILL PANELS SHALL BE OF AN
 APPROVED SAFETY GLAZING MATERIAL THAT CONFORMS TO THE
 PROVISIONS OF SECTION 2406.1.1. FOR ALL GLAZING TYPES,
 THE MINIMUM NOMINAL THICKNESS SHALL BE 1/4 INCH (6.4
 MM).
  
 4) CONVENIENCE STAIR - PLEASE PROVIDE THE STAIR DETAILS
 - FRAME TYPE, ATTACHMENTS TO EXISTING STRUCTURE ETC.