| Permit Number |
22011278 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-24 10:10:37 | OFFICE BUILDOUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) ADDED CONVENIENCE STAIR - IS THE SLAB CUT EXISTING? | | | - PLEASE SHOW THE STRUCTURAL DETAILS FOR THE SLAB CUT | | | AND REPAIR. | | | | | | 2) CONVENIENCE STAIR - PLEASE SHOW THE RISERS TO BE | | | CLOSED OR LESS THAN 4" OPENING PER FBC 1011.5.5.3 SOLID | | | RISERS. | | | RISERS SHALL BE SOLID. | | | | | | EXCEPTIONS: (1) SOLID RISERS ARE NOT REQUIRED FOR | | | STAIRWAYS THAT ARE NOT REQUIRED TO COMPLY WITH SECTION | | | 1009, PROVIDED THAT THE OPENING BETWEEN TREADS DOES NOT | | | PERMIT THE PASSAGE OF A SPHERE WITH A DIAMETER OF 4 | | | INCHES (102 MM). | | | | | | 3) CONVENIENCE STAIR - PLEASE PROVIDE A STATEMENT ON | | | THE DRAWINGS THAT THE GLASS IN THE GUARD RAILS COMPLY | | | WITH FBC 2407.1 MATERIALS. | | | GLASS USED IN A HANDRAIL, GUARDRAIL OR GUARD SECTION | | | SHALL BE LAMINATED GLASS CONSTRUCTED OF FULLY TEMPERED | | | OR HEAT-STRENGTHENED GLASS AND SHALL COMPLY WITH | | | CATEGORY II OR CPSC 16 CFR PART 1201 OR CLASS A OF ANSI | | | Z97.1. GLAZING IN RAILING IN-FILL PANELS SHALL BE OF AN | | | APPROVED SAFETY GLAZING MATERIAL THAT CONFORMS TO THE | | | PROVISIONS OF SECTION 2406.1.1. FOR ALL GLAZING TYPES, | | | THE MINIMUM NOMINAL THICKNESS SHALL BE 1/4 INCH (6.4 | | | MM). | | | | | | 4) CONVENIENCE STAIR - PLEASE PROVIDE THE STAIR DETAILS | | | - FRAME TYPE, ATTACHMENTS TO EXISTING STRUCTURE ETC. |
|