| Plan Review Notes For Permit 22011272 |
| Permit Number |
22011272 |
|
| Review Stop |
SIGNATURE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-22 11:23:42 | ) THERE ARE 3 FLOOR PLANS SUBMITTED BY THE CONTRACTOR. | | | THERE IS NO NAME IDENTIFYING WHO DREW THE PLANS. | | | CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE CONTRACTOR | | | (QUALIFIER) THAT CREATED / DREW THE SET OF PLANS WILL | | | NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. | | | PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE | | | NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS | | | DRAWN. | | | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE | | | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) | | | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) | | | REQUIRES THE CONTRACTOR FOR THAT TRADE THAT WILL BE | | | LICENSED IN THAT TRADE, WILL ALSO BE THE CONTRACTOR | | | THAT DESIGNS THE SYSTEM UNDER THAT TRADE. THE | | | CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF | | | PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF | | | THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND | | | LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND | | | PLANS DRAWN. | | | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE | | | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR | | | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE | | | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD | | | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND | | | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER | | | ONE SHEET. | | | | | | |
|