Plan Review Notes
Plan Review Notes For Permit 22011240
Permit Number 22011240
Review Stop B
Sequence Number 1
Notes
Date Text
2022-03-02 16:03:41ROOF TOP EQUIPMENT
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ON THE PROVIDED ENGINEERING FOR THE AC STAND -
 PLEASE CIRCLE THE STAND DESIGN TO BE USED FROM THE
 SCHEDULES.
  
 2) PLEASE SHOW THE WIDTH OF THE MECHANICAL UNIT AND THE
 CLEARANCE FROM THE ROOF TO THE BOTTOM OF THE STAND -
 FBC 1510.10 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1510.10.
  
 3) PLEASE SHOW THE HEIGHT OF THE BUILDING - NEEDED TO
 DETERMINE THE WIND DESIGN PRESSURES.
  