| Plan Review Notes For Permit 22011240 |
| Permit Number |
22011240 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-02 16:03:41 | ROOF TOP EQUIPMENT | | | | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) ON THE PROVIDED ENGINEERING FOR THE AC STAND - | | | PLEASE CIRCLE THE STAND DESIGN TO BE USED FROM THE | | | SCHEDULES. | | | | | | 2) PLEASE SHOW THE WIDTH OF THE MECHANICAL UNIT AND THE | | | CLEARANCE FROM THE ROOF TO THE BOTTOM OF THE STAND - | | | FBC 1510.10 MECHANICAL UNITS. | | | ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS | | | RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF | | | SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE | | | UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM | | | CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1510.10. | | | | | | 3) PLEASE SHOW THE HEIGHT OF THE BUILDING - NEEDED TO | | | DETERMINE THE WIND DESIGN PRESSURES. | | | |
|