| Plan Review Notes For Permit 22011226 |
| Permit Number |
22011226 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-24 12:46:14 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L. | | | FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING | | | COMMENTS: | | | | | | 1) THE PLANS INDICATE THERE WILL BE REPLACEMENT OF | | | FLOORING WITHOUT THE DOCUMENTS IDENTIFYING MATERIALS | | | BEING USED, PLEASE PROVIDE THE PRODUCT SPECS FOR ANY | | | FLOORING, UNDERLAYMENT, AND THEIR FIRE RATING INCLUDE | | | THE FIRE RATING. | | | - PER NFPA 101 CHAPTER 10, 10.2.7.2 | | | SHALL HAVE A MINIMUM CRITICAL RADIANT FLUX OF 0.1 | | | W/CM2. | | | | | | 2) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL | | | AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE | | | AND COMPLIANCE BY CERTIFIED CONTRACTORS. | | | | | | 3) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE | | | ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND | | | SHOP DRAWINGS BY CERTIFIED CONTRACTORS. | | | | | | 4) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL | | | REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION | | | PERIODS. | | | | | | | | | CAITLIN L. FRANCIS | | | FIRE INVESTIGATOR | | | 561-804-4728 | | | [email protected] | | | |
|