| | BUILDING REVIEW DENIED: |
| | |
| | THE PRIOR PLAN REVIEW COMMENTS HAVE NOT BEEN ANSWERED. |
| | THE FOLLOWING ARE REQUIRED: |
| | TEST REPORTS FOR AN UNDERLAYMENT THAT HAS BEEN TESTED |
| | AND APPROVED FOR USE WITH VINYL FLOORING OVER A 6" |
| | CONCRETE DECK WITH NO DROPPED CEILING. |
| | |
| | TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON THE |
| | EXISTING SITE CONDITIONS. |
| | TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S: |
| | E-84, E-90 & E-492. |
| | ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. |
| | |
| | FBC 603.1 FLAME SPREAD - ASTM E 84-09 |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | |
| | |
| | |
| | |
| | |