Plan Review Notes
Plan Review Notes For Permit 22011209
Permit Number 22011209
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-02-23 12:32:09THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS
 APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT.
  
  
 7.2.1.5.6 DOOR HARDWARE RELEASE OF ELECTRICALLY LOCKED
 EGRESS
 DOOR ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE
 PERMITTED TO BE EQUIPPED WITH APPROVED ELECTRICAL
 LOCKING SYSTEMS
 RELEASED BY THE OPERATION OF DOOR HARDWARE PROVIDED
 THAT ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE HARDWARE FOR EGRESS-SIDE OCCUPANT RELEASE OF
 THE ELECTRICAL
 LOCK IS AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY
 OPERATED IN THE DIRECTION OF EGRESS UNDER ALL LIGHTING
 CONDITIONS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE
 DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE DIRECTLY INTERRUPTS THE
 POWER SUPPLY TO
 THE ELECTRIC LOCK AND UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION
 OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY ELECTRICALLY
 UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
  
 7.2.1.6.1.2 THE PROVISIONS OF 7.2.1.6.2 FOR
 SENSOR-RELEASE OF ELECTRICAL
 LOCKING SYSTEMS SHALL NOT APPLY TO DOOR ASSEMBLIES WITH
 DELAYED-EGRESS
 ELECTRICAL LOCKING SYSTEMS.
  
  
 7.2.1.6.2 SENSOR-RELEASE OF ELECTRICAL LOCKING SYSTEMS.
 WHERE PERMITTED
 IN CHAPTERS 11 THROUGH 43, DOOR ASSEMBLIES IN THE MEANS
 OF EGRESS
 SHALL BE PERMITTED TO BE EQUIPPED WITH SENSOR-RELEASE
 ELECTRICAL LOCKING
 SYSTEM HARDWARE PROVIDED THAT ALL OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO ELECTRICALLY
 UNLOCK THE DOOR LEAF IN THE DIRECTION OF EGRESS UPON
 DETECTION
 OF AN APPROACHING OCCUPANT.
 (2) DOOR LEAVES SHALL AUTOMATICALLY ELECTRICALLY UNLOCK
 IN THE DIRECTION
 OF EGRESS UPON LOSS OF POWER TO THE SENSOR OR TO THE
 PART OF THE
 LOCKING SYSTEM THAT ELECTRICALLY LOCKS THE DOOR LEAVES.
 (3) DOOR LOCKS SHALL BE ARRANGED TO ELECTRICALLY UNLOCK
 IN THE DIRECTION
 OF EGRESS FROM A MANUAL RELEASE DEVICE COMPLYING WITH
 ALL OF THE
 FOLLOWING CRITERIA:
  
 (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE
 EGRESS SIDE,
 40 IN. TO 48 IN. (1015 MM TO 1220 MM ) VERTICALLY ABOVE
 THE
 FLOOR, AND WITHIN 60 IN. (1525 MM) OF THE SECURED DOOR
 OPENINGS,
 EXCEPT AS OTHERWISE PERMITTED BY 7.2.1.6.2(3)(C).
 (B) THE REQUIREMENT OF 7.2.1.6.2(3)(A) TO LOCATE THE
 MANUAL RELEASE
 DEVICE WITHIN 60 IN. (1525 MM) OF THE SECURED DOOR
 OPENING
 SHALL NOT APPLY TO PREVIOUSLY APPROVED EXISTING
 INSTALLATIONS.
 (C) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND
 CLEARLY IDENTIFIED BY A SIGN THAT READS AS FOLLOWS:
 PUSH TO
 EXIT.
 (D) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT
 INTERRUPTION OF POWER TO THE ELECTRICAL LOCK ?
 INDEPENDENT OF
 THE LOCKING SYSTEM ELECTRONICS ? AND THE LOCK SHALL
 REMAIN
 UNLOCKED FOR NOT LESS THAN 30 SECONDS.
 (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM, IF PROVIDED,
 SHALL AUTOMATICALLY ELECTRICALLY UNLOCK THE DOOR LEAVES
 IN
 THE DIRECTION OF EGRESS, AND THE DOOR LEAVES SHALL
 REMAIN ELECTRICALLY
 UNLOCKED UNTIL THE FIRE-PROTECTIVE SIGNALING SYSTEM HAS
 BEEN MANUALLY
 RESET.
 (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE BUILDING
 FIRE-PROTECTIVE SIGNALING SYSTEM SPECIFIED IN
 7.2.1.6.2(4) SHALL NOT
 BE REQUIRED TO UNLOCK THE DOOR LEAVES.
 (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE DETECTION
 SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY ELECTRICALLY
 UNLOCK THE DOOR
 LEAVES IN THE DIRECTION OF EGRESS, AND THE DOOR LEAVES
 SHALL REMAIN
 ELECTRICALLY UNLOCKED UNTIL THE FIRE-PROTECTIVE
 SIGNALING SYSTEM HAS
 BEEN MANUALLY RESET.
 (7) THE EGRESS SIDE OF SENSOR-RELEASE ELECTRICALLY
 LOCKED EGRESS DOORS,
 OTHER THAN EXISTING SENSOR-RELEASE ELECTRICALLY LOCKED
 EGRESS DOORS,
 SHALL BE PROVIDED WITH EMERGENCY LIGHTING IN ACCORDANCE
 WITH
 SECTION 7.9.
 (8) HARDWARE FOR NEW INSTALLATIONS SHALL BE LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
  
  
  