| 2022-02-28 10:19:55 | FIRE REVIEW COMMENTS: | | | THE PLAN SUBMITTED DOES NOT INCLUDE: | | | ? THE SEQUENCE OF OPERATION FOR THE ACCESS CONTROL | | | SYSTEM AND TYPE SYSTEM | | | ? IF THIS SYSTEM WILL BE CONNECTED TO THE FIRE ALARM | | | PANEL | | | ? EQUIPMENT MOUNTING HEIGHT | | | ? IF THE SYSTEM WILL ALLOW FOR FREE EGRESS | | | ? EMERGENCY LIGHTING IN THE RECEPTION AREA | | | NFPA 101, 7.2.1.6.2 | | | |
|