| Plan Review Notes For Permit 22011134 |
| Permit Number |
22011134 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-19 16:01:44 | 1ST REVIEW FMC | | | PERMIT: 22011134 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS AND THE MECHANICAL | | | EQUIPMENT SIZING CALCULATIONS FOR THIS GARAGE OR | | | PROVIDE A DEHUMIDIFIER CONTROLLED BY THE HUMIDISTAT. IF | | | USING ANYTHING OTHER THAN A DEHUMIDIFIER WOULD REQUIRE | | | THE AREA TO MEET THE ENERGY CODE. FEC R402, FEC | | | R403.7.1 | | | | | | 2) REVISED THE PLAN TO SHOW THE CONDENSATE PIPING AND | | | TERMINATION LOCATION. FRC M1411.3 | | | | | | 3) REVISE THE PLAN TO SHOW THE CONDENSING UNIT TIE DOWN | | | METHOD. FRC M1307.2 | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|