2022-04-25 07:27:512ND PLUMBING REVIEW
  
 V7 FBC P - 2020 FLORIDA PLUMBING CODE
 V7 FBC EX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FBC EC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
  
 1. DONE
 2. V7 FBC P - 607.1.1/607.1.2 - PLEASE DETAIL THE
 LIMITING DEVICE(S) AND CONFIGURATION FOR HOT WATER AND
 TEMPERED WATER DELIVERY. THE THERMOSTAT ON THE WATER
 HEATER CANNOT BE THE LIMIT FOR HOT WATER/TEMPERED WATER
 DELIVERY. THIS CAN BE ACHIEVED BY A DEVICE AT THE WATER
 HEATING SOURCE OR AT EACH FIXTURE INDIVIDUALLY. THIS
 WOULD BE IN ADDITION TO THE LIMITING DEVICE FOR
 TEMPERED WATER DELIVERY. TEMPERED WATER MUST BE LIMITED
 BY A DEVICE THAT CONFORMS TO ASSE 1070 AND BE LESS THAN
 110 DEGREES F FOR PUBLIC HAND WASHING OR COLD WATER
 ONLY SUPPLIED. (V7 FBC P 419.5) -------------CHANGES DO
 NOT ADDRESS THE HOT WATER DELIVERY PER 607.1.1. PLEASE
 SHOW A DETAIL THAT SHOWS A LIMIT FOR "HOT WATER"
 DELIVERY OTHER THAN THE THERMOSTAT ON THE WATER HEATER.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  