Plan Review Notes
Plan Review Notes For Permit 22011125
Permit Number 22011125
Review Stop P
Sequence Number 1
Notes
Date Text
2022-03-14 13:14:251ST PLUMBING REVIEW
  
 V7 FBC P - 2020 FLORIDA PLUMBING CODE
 V7 FBC EX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FBC EC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
  
 1. V7 FBC P 1003.3.1 - GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES SHALL RECEIVE WASTE
 ONLY FROM FIXTURES AND EQUIPMENT THAT ALLOW FATS, OILS
 OR GREASE TO BE DISCHARGED. HAND SINKS ARE NOT DESIGNED
 FOR F.O.G. DISCHARGE AND CANNOT BE CONNECTED TO THE
 GREASE WASTE.
  
 2. V7 FBC P - 607.1.1/607.1.2 - PLEASE DETAIL THE
 LIMITING DEVICE(S) AND CONFIGURATION FOR HOT WATER AND
 TEMPERED WATER DELIVERY. THE THERMOSTAT ON THE WATER
 HEATER CANNOT BE THE LIMIT FOR HOT WATER/TEMPERED WATER
 DELIVERY. THIS CAN BE ACHIEVED BY A DEVICE AT THE WATER
 HEATING SOURCE OR AT EACH FIXTURE INDIVIDUALLY. THIS
 WOULD BE IN ADDITION TO THE LIMITING DEVICE FOR
 TEMPERED WATER DELIVERY. TEMPERED WATER MUST BE LIMITED
 BY A DEVICE THAT CONFORMS TO ASSE 1070 AND BE LESS THAN
 110 DEGREES F FOR PUBLIC HAND WASHING OR COLD WATER
 ONLY SUPPLIED. (V7 FBC P 419.5)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  