Plan Review Notes
Plan Review Notes For Permit 22011125
Permit Number 22011125
Review Stop M
Sequence Number 1
Notes
Date Text
2022-03-22 11:25:121ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22011125
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A STATEMENT ON THE MECHANICAL DRAWINGS
 STATING THAT THE KITCHEN HOOD WILL REQUIRE A SEPARATE
 PERMIT AND PLAN REVIEW AS IT WILL NOT BE REVIEWED UNDER
 THIS APPLICATION.
  
 2) PLEASE ADD A STATEMENT ON THE MECHANICAL DRAWINGS
 STATING THAT THE WALK-IN COOLER WILL REQUIRE A SEPARATE
 PERMIT AND PLAN REVIEW AS IT WILL NOT BE REVIEWED UNDER
 THIS APPLICATION
  
 3) THE DUCT ENCLOSURE SHALL SERVE A SINGLE GREASE DUCT
 AND SHALL NOT CONTAIN OTHER DUCTS, PIPING OR WIRING
 SYSTEMS. FBC M 506.3.11
  
 4) PLEASE SHOW THAT THE RETURN SERVING THE KITCHEN FROM
 AHU-1-01B IS 10 FEET FROM THE COOKING APPLIANCES. FBC M
 601.5 EXCEPTION 1
  
 5) I SEE A PIZZA PREP AREA BUT I DO NOT SEE A PIZZA
 OVEN ON THE EQUIPMENT SCHEDULE. PLEASE EXPLAIN HOW THE
 PIZZAS WILL BE COOKED.
  
 6) SHEET M201 KEY NOTE 3 INDICATES A NEW FIRE RATED
 SHAFT. SHEET S-1 DOES NOT SHOW THIS RATED SHAFT ON THE
 2ND FLOOR OR THE ROOF. PLEASE SHOW A DETAIL OF THIS
 ENTIRE SHAFT. FBC 107.2.1
  
 7) PLEASE SHOW THAT THE KEF AND MAKE-UP AIR
 TERMINATIONS ARE 10 FEET FROM THE ROOFS EDGE OR THERE
 IS A GUARD IN PLACE. FBC M 304.11
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  