Plan Review Notes
Plan Review Notes For Permit 22011125
Permit Number 22011125
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-03-11 12:29:20THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET CS 0.0 - UNDER THE CODE ANALYSIS THERE IS AN
 INDICATION OF A BUIDING CODE 903 FIRE SPRINKLERS
 REQUIRED & PROVIDED.
  
 THERE IS NO INDICATION OF AN EXISTING FIRE SPRINKLER;
 HOWEVER, THERE IS RECORD OF ONE AT THIS ADDRESS.
  
 IF THERE IS AN EXISTING SYSTEM:
  
 THE FIRE SPRINKLER SYSTEM SHALL BE MAINTAINED
 THROUGHOUT DEMO AND RECONSTRUCTION.
  
 ANY WORK ON A FIRE SPRINKLER SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
  
 1A) FIRE SPRINKLER ALARM - THERE IS RECORD OF A FIRE
 ALARM SYSTEM AT THIS ADDRESS.
  
 THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE MONITORED.
  
 THE FIRE ALARM SYSTEM SHALL BE MAINTAINED THROUGHOUT
 DEMO AND RECONSTRUCTION.
  
 ANY WORK ON A FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 THE FIRE SPRINKLER ALARM PERMIT SHALL BE SUBMITTED
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLEDGEMENT.
  
  
 2) SHEET A 0.1 - THE INDICATED OCCUPANCY LOAD 216
 APPEARS TO BE TOO HIGH.
  
 THE CALCULATION FOR WAITING INDICATES 5 NET OF 203 SQ
 FT = 41. PER NFPA CH 7 MEANS OF EGRESS 7 NET IS
 REQUIRED = 29.
  
 THE AREA FOR THIS CALCULATION LOOKS SMALL WITH THE
 DIMENSIONS NOT INDICATED TO VERIFY THE SG FT NUMBER.
 ADDITIONALLY, THE AREA IN FRONT OF THE DOOR IS HATCHED
 BUT CAN NOT BE USED FOR STANDING ROOM.
  
 THE CALCULATION OF THE SEATING AREA PLUS THE BOOTHS IS
 NOT CORRECT. THE SEATING AREA IS TO BE INCLUDED OF THE
 BOOTHS/CHAIRS, NOT SEPARATE.
  
 PLEASE REVIEW AND PROVIDE CORRECTION PER THE
 REQUIREMENTS OF NFPA CH 12, NEW ASSEMBLY AND CH 7 MEANS
 OF EGRESS.
  
  
  
 3) SHEET CA THRU CA 4 - THE HOOD AND SUPPRESSION
 SYSTEMS SHALL BE INSTALLED UNDER SEPARATE PERMIT AND
 SHOP DRAWINGS.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 4) SHEET E 301 - THERE DOES NOT APPEAR TO BE
 INDICATIONS OF EXIT SIGNS, EXISTING NOR NEW, AT THE
 FROM DOOR AND THE BACK KITCHEN EXIT DOOR.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE JUSTIFICATION
 INCLUDING CODE REFERENCES AS TO WHY THEY ARE NOT
 REQUIRED PER NFPA 101, CH 12 & CH 7
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL