| 2022-03-11 12:29:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET CS 0.0 - UNDER THE CODE ANALYSIS THERE IS AN |
| | INDICATION OF A BUIDING CODE 903 FIRE SPRINKLERS |
| | REQUIRED & PROVIDED. |
| | |
| | THERE IS NO INDICATION OF AN EXISTING FIRE SPRINKLER; |
| | HOWEVER, THERE IS RECORD OF ONE AT THIS ADDRESS. |
| | |
| | IF THERE IS AN EXISTING SYSTEM: |
| | |
| | THE FIRE SPRINKLER SYSTEM SHALL BE MAINTAINED |
| | THROUGHOUT DEMO AND RECONSTRUCTION. |
| | |
| | ANY WORK ON A FIRE SPRINKLER SYSTEM SHALL BE DONE UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | |
| | 1A) FIRE SPRINKLER ALARM - THERE IS RECORD OF A FIRE |
| | ALARM SYSTEM AT THIS ADDRESS. |
| | |
| | THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE MONITORED. |
| | |
| | THE FIRE ALARM SYSTEM SHALL BE MAINTAINED THROUGHOUT |
| | DEMO AND RECONSTRUCTION. |
| | |
| | ANY WORK ON A FIRE ALARM SYSTEM SHALL BE DONE UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | THE FIRE SPRINKLER ALARM PERMIT SHALL BE SUBMITTED |
| | UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | 2) SHEET A 0.1 - THE INDICATED OCCUPANCY LOAD 216 |
| | APPEARS TO BE TOO HIGH. |
| | |
| | THE CALCULATION FOR WAITING INDICATES 5 NET OF 203 SQ |
| | FT = 41. PER NFPA CH 7 MEANS OF EGRESS 7 NET IS |
| | REQUIRED = 29. |
| | |
| | THE AREA FOR THIS CALCULATION LOOKS SMALL WITH THE |
| | DIMENSIONS NOT INDICATED TO VERIFY THE SG FT NUMBER. |
| | ADDITIONALLY, THE AREA IN FRONT OF THE DOOR IS HATCHED |
| | BUT CAN NOT BE USED FOR STANDING ROOM. |
| | |
| | THE CALCULATION OF THE SEATING AREA PLUS THE BOOTHS IS |
| | NOT CORRECT. THE SEATING AREA IS TO BE INCLUDED OF THE |
| | BOOTHS/CHAIRS, NOT SEPARATE. |
| | |
| | PLEASE REVIEW AND PROVIDE CORRECTION PER THE |
| | REQUIREMENTS OF NFPA CH 12, NEW ASSEMBLY AND CH 7 MEANS |
| | OF EGRESS. |
| | |
| | |
| | |
| | 3) SHEET CA THRU CA 4 - THE HOOD AND SUPPRESSION |
| | SYSTEMS SHALL BE INSTALLED UNDER SEPARATE PERMIT AND |
| | SHOP DRAWINGS. |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 4) SHEET E 301 - THERE DOES NOT APPEAR TO BE |
| | INDICATIONS OF EXIT SIGNS, EXISTING NOR NEW, AT THE |
| | FROM DOOR AND THE BACK KITCHEN EXIT DOOR. |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE JUSTIFICATION |
| | INCLUDING CODE REFERENCES AS TO WHY THEY ARE NOT |
| | REQUIRED PER NFPA 101, CH 12 & CH 7 |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |