Plan Review Notes
Plan Review Notes For Permit 22011100
Permit Number 22011100
Review Stop P
Sequence Number 1
Notes
Date Text
2022-01-28 09:46:1001/28/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER
 DIAGRAM FOR WATER PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 2. WOULD YOU PLEASE SHOW THE SHUT-OFF VALVE FOR EACH
 DWELLING ON THE ISOMETRIC PER THE 2020 FBC SEC. R
 2903.9.1 SERVICE VALVE.
  
 3. WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR
 SHUTTING OFF WITHOUT MOVING UNITS, 2020 FBC SEC. R
 2903.9.3 FIXTURE VALVES AND ACCESS. ACCESSIBLE
 SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL OF AN ACCESS
 PANEL OR SIMILAR REMOVABLE OBSTRUCTION, AND PLEASE SHOW
 ON THE SIDE.
  
 4. WOULD YOU PLEASE PROVIDE CLEANOUT OUTSIDE OF EACH
 DWELLING 2020 FBC R 3005.2.1HORIZONTAL DRAINS AND
 BUILDING DRAINS?
  
 5. ON SHEET P-1 DETAIL #1;
  
 A. WOULD YOU PLEASE SHOW THE VENTING AND SUPPLY FOR THE
 ISOMETRIC DIAGRAM PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 B. WOULD YOU PLEASE LABEL ROOMS, W/M, KITCHEN, AND
 BATHROOMS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. ON SHEET P-1.1 DETAIL #2;
  
 A. THE LAV IS SHOWN IN THE WRONG DIRECTION. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE LAUNDRY ROOM IS CONNECTED TO THE WATER CLOSET,
 AND IT SHALL BE DOWNSTREAM OF A BATHROOM GROUP PER THE
 2020 FBC SECTION R 3108.1 HORIZONTAL WET VENT
 PERMITTED.
  
 C. THERE ARE TWO SANITARY RISER DIAGRAM DETAIL 1. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. IN-UNIT D ISOMETRIC DIAGRAM, WOULD YOU PLEASE SHOW
 THE VENTING AND SUPPLY PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 E. IN UNIT C, THE ISOMETRIC DIAGRAM SHOWS THE LAUNDRY
 ROOM IS LABELED AS A WATER CLOSET, AND WOULD YOU PLEASE
 SHOW THE VENTING AND SUPPLY PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 F. IN THE BATHROOM ON THE SECOND FLOOR NEXT TO THE AC
 UNIT AND IN-UNIT C BATHROOM WITH TUB, THERE IS A WATER
 CLOSET AND TUB THAT ARE NOT VENTED CORRECTLY. A DOUBLE
 WYE IS A FITTING THAT WILL VENT BOTH. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 G. WOULD YOU PLEASE LABEL ROOMS, W/M, KITCHEN, AND
 BATHROOMS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. THESE ARE MULTI-FAMILY DWELLINGS, AND WATER USERS
 WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW
 ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF
 HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER
 THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND
 THEIR CONNECTION CONTROL PROGRAM.
  
 8. THE IRRIGATION SYSTEM WILL REQUIRE A REDUCED
 PRESSURE ZONE VALVE PER THE DEGREE OF HAZARD DUE TO HIS
 BEING A COMMERCIAL PROPERTY PER THE 202 FBC TABLE R
 2902.3 APPLICATION FOR BACKFLOW PREVENTERS.
  
 9. THE COVER SHEET UNDER-OCCUPANCY CLASSIFICATION SAYS
 RM, AND THAT CALCIFICATION DOES NOT EXIST IN THE FBC.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  