| 2022-02-02 11:40:12 | ELECTRIC REVIEW FAILED |
| | 1) ELECTRICAL SERVICES AS DETAILED DO NOT COMPLY WITH |
| | NEC 230.2. PLEASE CORRECT TO BRING INTO COMPLIANCE. |
| | 2) PROVIDE RECEPTACLES AS REQUIRED PER NEC 210.52 |
| | (E)(1) & (3) |
| | 3) UNITS "C&D" DO NOT DETAIL SMOKE ALARMS AS REQUIRED |
| | PER FBC RE 2020, 7TH EDITION |
| | 4) ELECTRICAL SUB PERMIT STATES WORK AS DEMO ONLY |
| | HOWEVER MAIN PERMIT STATES INTERIOR REMODEL. PLEASE |
| | CLARIFY AS PER F.BC. [A] 107.2.1 |
| | 5) VALUE FOR WORK STATED ON PERMIT APPLICATION |
| | ($40,000) APPEARS LOW. PROVIDE A BREAKDOWN OF ALL |
| | MATERIALS AND LABOR, OR, AT YOUR DISCRETION, PROVIDE A |
| | SIGNED CONTRACTOR OR PROVIDE A REASONABLE VALUE. WPB |
| | F.B.C. 109.3 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |