Plan Review Notes
Plan Review Notes For Permit 22011094
Permit Number 22011094
Review Stop P
Sequence Number 1
Notes
Date Text
2022-12-13 16:53:331ST REVIEW FBC-2020 PLUMBING
 PERMIT-22011094
 12/13/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS DO NOT CLEARLY ILLUSTRATE IF A ROOF
 DRAINAGE SYSTEM WILL BE INSTALLED TO CONVEY RAINWATER
 FROM THE NEW ROOFS TO AN APPROVED DISPOSAL LOCATION-
 SEC. 1102.1 FBC P.
  
 ROOF DRAINAGE PLANS SHALL INCLUDE:
 A) RAINFALL RATE AND ROOF SQUARE FOOT AND GPM FLOW
 CALCULATIONS- SEC. 1106.1
 B) A STORM DRAIN ISOMETRIC DRAWING SHOWING THE ROOF
 DRAIN VERTICAL LEADERS AND HORIZONTAL STORM DRAIN SIZES
 AND LOCATIONS OF REQUIRED CLEANOUTS- SECS. 1106.1,
 1106.1, & 1108.1.
 C) SIZING CALCULATIONS AND LOCATIONS OF SECONDARY ROOF
 DRAINS IF REQUIRED- SEC.1108.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  