| 2022-01-27 14:20:42 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22011084 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE REMOVE THE RETURN AIR DUCT AND GRILL FROM THE | | | MASTER BATH. FBC RES M1602.2-4 | | | | | | 2) PLEASE SHOW THE CONDENSATE DRAIN LINES MATERIAL, | | | SIZE AND TERMINATION LOCATION. FBC RES M1411.3 | | | | | | 3) PLEASE PROVIDE THE BATH EXHAUST FANS CFM?S. FBC RES | | | M1507 | | | | | | 4) IS THERE GOING TO BE AN EXHAUST HOOD OVER THE RANGE | | | IN THE KITCHEN? IF SO, IS IT DUCTED TO THE OUTDOORS? IF | | | SO, PLEASE PROVIDE THE CFM?S REQUIRED BY THE EXHAUST | | | FAN AND SHOW IF MAKE UP AIR IS REQUIRED. FBC RES | | | M1503.4 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|