| Plan Review Notes For Permit 22011081 |
| Permit Number |
22011081 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-15 11:40:09 | BUILDING PROVISO: THE DESIGNER OF RECORD STATING NEW | | | ENTRY DOORS AND SIDELIGHT TO BE FIRE RATED. DOOR | | | SCHEDULE,NOTES #1 STATE ENTRY DOOR TO BE | | | 1 HOUR FIRE RATED. THE DESIGNER OF RECORD CAN DESIGN TO | | | A MORE STRINGENT STANDARD THAN THE CODE. CONTRACTOR HAS | | | COME INTO THE BUILDING DEPARTMENT STATING ONTHE WALL | | | ABOVE IS PRINTED 1 HOUR FIRE RATED WALL FOR THE CODE | | | THAT WAS AFFECT AT THAT TIME. THE 2020 FBC-BUILDING | | | CODE DOES NOT REQUIRE A FIRE RATED CORRIDOR PER TABLE | | | 1020.1 BUILDING OCCUPANCY/ FIRE SPRINKLERED. PLEASE | | | REVIEW TABLE 716.5 FOR 1 HOUR FIRE RATINGS AND SIZE OF | | | VISION PANELS IF THE DESIGNER OF RECORD IS TO MAINTAIN | | | A 1 HOUR RATING ON THE GLAZING!!!!!!!!!! TABLE 716.5 | | | WHERE REQUIRED FIRE RATING IS REQUIRED FOR SPRINKLERED | | | BUILDINGS 0.5 HR. & 20 MIN. DOOR RATING. | | | JIM WITMER BUILDING PLAN REVIEW 02/15/2022 |
|