| 2022-03-23 15:42:18 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22011077. |
| | |
| | NOTE: |
| | ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1 |
| | FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| | |
| | NOTE: |
| | LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING. |
| | SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 |
| | FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| | |
| | 1-LOT DRAINAGE |
| | 1- PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE |
| | DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT |
| | WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES. |
| | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS |
| | AND SEC. 110.9 CITY AMENDMENTS. |
| | NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| | GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| | ADJACENT PROPERTIES. |
| | |
| | 2-ENERGY CALCULATIONS SUBMITTED: |
| | NOTE: THIS HOUSE IS A CONTRIBUTING HISTORIC HOUSE. |
| | ENERGY CALCULATIONS ARE NOT REQUIRED. BUT IF APPLICANT |
| | WANTS THEM TO BE PART OF THE CONSTRUCTION DOCUMENTS, |
| | THEN REVISE THEM AS FOLLOWS: |
| | |
| | A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE |
| | CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S |
| | ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY |
| | THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY |
| | SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | B)A/C AREA SPECIFIED ON PAGE 1 DOESN'T MATCH AREA |
| | SPECIFIED ON PLANS. REVISE AS REQUIRED TO MATCH. |
| | SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| | |
| | C) DOORS INFORMATION SPECIFIED ON PAGE 3 DOESN'T MATCH |
| | PLANS AND PRODUCT APPROVALS. REVISE AS REQUIRED TO |
| | MATCH. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| | NOTE: DOORS TO BE CONSIDERED ARE THE ONES SEPARATING |
| | A/C AREA FROM NON A/C AREAS. |
| | |
| | D) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| | LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | 3-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)METAL SHINGLES. PROVIDE COMPLETE AND CURRENT APPROVED |
| | PRODUCT APPROVAL. NEED COMPLETE FLORIDA PRODUCT |
| | APPROVAL, INCLUDING FLORIDA PRODUCT APPROVAL COVER PAGE |
| | SHOWING THE CURRENT CODE OR MIAMI DADE NOA. |
| | IF NONE OF THESE OPTIONS IS AVAILABLE, THEN |
| | MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL BY |
| | SUBMITTING COMPLETE ENGINEERING SIGNED AND SEALED |
| | DRAWINGS FOR BUILDING OFFICIAL APPROVAL. FAC |
| | 61G20-3.001. |
| | |
| | B)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| | TO AVOID DELAYS/CONFLICTS). |
| | |
| | C)INSWING ENTRY DOOR AS SHOWN ON PLANS. |
| | |
| | D)GARAGE EXTERIOR SWING DOOR AS SHOWN ON PLANS. |
| | |
| | E) STORAGE EXTERIOR DOOR AS SHOWN ON PLANS. |
| | |
| | F)CABANA BATH DOOR AS SHOWN ON PLANS. |
| | |
| | G) UNDERLAYMENT SPECIFIED ON PLANS FOR METAL SHINGLES. |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 5- WIND RESISTANCE OF EXTERIOR SOFFITS: ENGINEER OF |
| | RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| | FOR THE SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH |
| | SEC. R704 FBC-RESIDENTIAL. |
| | NOTE: PLANS SPECIFY T & G WOOD CEILING ALT. W.L. & |
| | STUCCO. PROVIDE COMPLETE DETAIL/SPECS FOR ALT. W.L. & |
| | STUCCO SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH WIND |
| | RESISTANCE. |
| | |
| | 6- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE R-20 |
| | INSULATION TO VERIFY COMPLIANCE WITH SEC. R316 |
| | FBC-RESIDENTIAL. |
| | NOTE: ENGINEER TO REVIEW AND APPROVE THE REPORT IN |
| | WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | 7- SPECIFY ATTIC ACCESS SIZE AND LOCATION IN NEW |
| | ADDITION. ALSO, SPECIFY SIZE FOR NEW ATTIC ACCESS SHOWN |
| | IN GARAGE AREA. SEC. R807 FBC-RESIDENTIAL. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| | REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |