Plan Review Notes
Plan Review Notes For Permit 22011040
Permit Number 22011040
Review Stop P
Sequence Number 2
Notes
Date Text
2022-07-25 18:45:432ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22011040
 7/25/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. THE
 REQUESTED RESPONSE TO COMMENTS NARRATIVE WAS NOT
 PROVIDED
  
 1) FAILED SHEET A101: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES. THE PLAN APPEARS TO SHOW A
 BUSINESS OCCUPANCY. PLEASE NOTE THAT DRINKING FOUNTAINS
 AND SERVICE SINKS ARE REQUIRED FIXTURES FOR BUSINESS
 OCCUPANCIES- SEE TABLE 403.1. FIXTURE CALCULATIONS AND
 SERVICE SINK NOT PROVIDED.
  
 4) FAILED. A101: INDICATE HOW HOT WATER WILL BE
 DELIVERED FROM THE SHOWER FAUCETS IN COMPLIANCE WITH
 SEC. 607.1 FBC P. SHOW THE LOCATION OF THE EXISTING
 WATER HEATER, OR PROVIDE A NEW WATER HEATER. A NEW
 WATER HEATER INSTALLATION WILL REQUIRE AN EQUIPMENT
 SCHEDULE ON THE PLAN, AND A MEANS OF CONTROLLING G
 THERMAL EXPANSION DETAILED- SECS. 502.1, 607.3 FBC P.
 A) PLEASE NOTE THAT A THERMOSTAT CONTROL FOR A WATER
 HEATER SHALL NOT SERVE AS THE TEMPERATURE LIMITING
 MEANS FOR THE PURPOSES OF COMPLYING WITH THE
 REQUIREMENTS OF THIS CODE FOR MAXIMUM ALLOWABLE HOT OR
 TEMPERED WATER DELIVERY TEMPERATURE AT FIXTURES. THE
 SOURCE OF THE HOT WATER AND TEMPERATURE LIMITING MEANS
 ARE NOT SHOWN.
  
 5) FAILED. A101: COLD WATER OR TEMPERED WATER SHALL BE
 DELIVERED FROM THE LAVATORIES IN COMPLIANCE WITH SEC.
 419.5 FBC P. PLEASE NOTE THAT TEMPERED WATER SHALL BE
 SUPPLIED THROUGH A WATER TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070- SEC. 607.1.2 FBC P. HOT
 WATER, NOT TEMPERED WATER IS BEING SUPPLIED TO THE NEW
 LAVATORIES
  
 6) FAILED. A101: PROVIDE A PLUMBING FIXTURE SCHEDULE-
 SEC. 405 FBC P. NOT PROVIDED
  
 7) FAILED. A101: PROVIDE A SLAB REPAIR DETAIL- SEC.
 107.2.1 WPB. NOT PROVIDED.
  
 8) FAILED ITEMS A, B, F, G, H, I, & J PROVIDE THE
 FOLLOWING DETAILS IN ACCORDANCE WITH SEC. 213.1 FBC
 ACCESSIBILITY CODE.
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3. NOT PROVIDED.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2. NOT PROVIDED.
 F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3 THE " MEASUREMENT
 IS TO THE FRAME OF THE MIRROR AND NOT THE REFLECTIVE
 SURFACE.
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. WATER CLOSET SIDE GRAB NOT
 SHOWN. REAR GRAB BAR IS SHOWN BUT MEASURMENTS NOT
 PROVIDED. THE 3'0" GRAB BAR HEIGHT MEASUREMENT SHOWN
 SHALL BE TO THE TOP OF THE GRIPPING SURFACES.
 H) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- SEC.
 604.6. NOT PROVIDED.
 I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7. NOT PROVIDED.
 J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2. NOT PROVIDED.
  
 9) SHOWERS: FAILED ITEMS A, B, C, D.
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 SHOWER- SEC. 608.2.2. PLEASE NOTE THAT THE LOCATION OF
 THE SHOWER, SHOWER CONTROLS, AND WATER CLOSET ARE NOT
 IN COMPLIANCE WITH SEC. 608.2.2.1 EXCEPTION: A LAVATORY
 COMPLYING WITH 606 SHALL BE PERMITTED ON ONE 30-INCH
 WIDE MINIMUM SIDE OF THE CLEARANCE PROVIDED THAT IT IS
 NOT ON THE SIDE OF THE CLEARANCE ADJACENT TO THE
 CONTROLS OR, WHERE PROVIDED, NOT ON THE SIDE OF THE
 CLEARANCE ADJACENT TO THE SHOWER SEAT. CORRECTIONS NOT
 PROVIDED. PLEASE NOTE A MINIMUM OF ONE OF THE SHOWERS
 SHALL BE ACCESSIBLE PER SEC. 213.3.6 FBC ACC. PLEASE
 REVIEW THE FOLLWING FBC ACC CODE SECTION-
  
 608.2.2.1 CLEARANCE.
 A 30-INCH WIDE MINIMUM BY 60 INCH LONG MINIMUM
 CLEARANCE SHALL BE PROVIDED ADJACENT TO THE OPEN FACE
 OF THE SHOWER COMPARTMENT.
 EXCEPTION: A LAVATORY COMPLYING WITH 606 SHALL BE
 PERMITTED ON ONE 30 INCH (760 MM) WIDE MINIMUM SIDE OF
 THE CLEARANCE PROVIDED THAT IT IS NOT ON THE SIDE OF
 THE CLEARANCE ADJACENT TO THE CONTROLS OR, WHERE
 PROVIDED, NOT ON THE SIDE OF THE CLEARANCE ADJACENT TO
 THE SHOWER SEAT.
  
 B) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECS. 608.3.2, 609.4. NOT PROVIDED.
  
 C) LOCATION OF CONTROLS, FAUCETS, AND SHOWER SPRAYS-
 SEC. 608.5.2. NOT PROVIDED.
  
 D) SHOWER SPRAY UNIT SPECIFICATIONS PER SEC. 608.6. NOT
 PROVIDED.
  
 NEW COMMENTS BASED ON RESUBMITTED A-101 PLAN.
 1) PROVIDE ACCESSIBLE DRINKING FOUNTAIN DETAILS. REFER
 TO SECTIONS 306, 307, AND 602 FBC ACC AND PROVIDE
 DRINKING FOUNTAIN INSTALLATION DETAILS AND ELEVATION
 VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS,
 AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 IN.
 CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH TO
 THE FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW HOW THE
 LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SECTION 307.2 PROTRUSION LIMITS.
  
 2) SANITARY ISOMETRIC: THE DRINKING FOUNTAIN DRAIN
 SHALL NOT CONNECT TO THE HORIZONTAL WET VENT FOR THE
 BATHROOMS. THE DRINKING FOUNTAINS SHALL BE INDIVIDUALLY
 VENTED AND THE DRAIN SHALL CONNECT EITHER UPSTREAM OR
 DOWNSTREAM OF THE WET VENT.
  
 3) SANITARY ISOMETRIC: REFER TO SEC. 904.1- THE VENT
 SYSTEM SERVING EACH BUILDING DRAIN SHALL HAVE NOT LESS
 THAN ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS. PLEASE
 SHOW THE LOCATION OF THE REQUIRED VENT.
  
 4) SHOWER CURB- THRESHOLDS FOR ACCESSIBLE ROLL IN
 SHOWERS SHALL BE MAXIMUM ?-INCH. THE DETAIL SHOWS A
 2-INCH THRESHOLD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  