| 2022-03-24 16:44:33 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22011040 |
| | 3/24/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A101: PROVIDE PLUMBING FIXTURE CALCULATIONS IN |
| | ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE |
| | THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF |
| | FIXTURES. THE PLAN APPEARS TO SHOW A BUSINESS |
| | OCCUPANCY. PLEASE NOTE THAT DRINKING FOUNTAINS AND |
| | SERVICE SINKS ARE REQUIRED FIXTURES FOR BUSINESS |
| | OCCUPANCIES- SEE TABLE 403.1. |
| | |
| | 2) A101: LABEL THE BATHROOMS AS MALE, FEMALE, OR |
| | FAMILY- SECS 403.2, 403.2.1, 403.4 FBC P. |
| | |
| | 3) PROVIDE A WATER RISER DRAWING- SEC. 107.3.5.1.3 WPB. |
| | |
| | 4) A101: INDICATE HOW HOT WATER WILL BE DELIVERED FROM |
| | THE SHOWER FAUCETS IN COMPLIANCE WITH SEC. 607.1 FBC P. |
| | SHOW THE LOCATION OF THE EXISTING WATER HEATER, OR |
| | PROVIDE A NEW WATER HEATER. A NEW WATER HEATER |
| | INSTALLATION WILL REQUIRE AN EQUIPMENT SCHEDULE ON THE |
| | PLAN, AND A MEANS OF CONTROLLING G THERMAL EXPANSION |
| | DETAILED- SECS. 502.1, 607.3 FBC P. A) PLEASE NOTE THAT |
| | A THERMOSTAT CONTROL FOR A WATER HEATER SHALL NOT SERVE |
| | AS THE TEMPERATURE LIMITING MEANS FOR THE PURPOSES OF |
| | COMPLYING WITH THE REQUIREMENTS OF THIS CODE FOR |
| | MAXIMUM ALLOWABLE HOT OR TEMPERED WATER DELIVERY |
| | TEMPERATURE AT FIXTURES. |
| | |
| | 5) A101: COLD WATER OR TEMPERED WATER SHALL BE |
| | DELIVERED FROM THE LAVATORIES IN COMPLIANCE WITH SEC. |
| | 419.5 FBC P. PLEASE NOTE THAT TEMPERED WATER SHALL BE |
| | SUPPLIED THROUGH A WATER TEMPERATURE LIMITING DEVICE |
| | THAT CONFORMS TO ASSE 1070- SEC. 607.1.2 FBC P. |
| | |
| | 6) A101: PROVIDE A PLUMBING FIXTURE SCHEDULE- SEC. 405 |
| | FBC P. |
| | |
| | 7) A101: PROVIDE A SLAB REPAIR DETAIL- SEC. 107.2.1 |
| | WPB. |
| | |
| | 8) PROVIDE THE FOLLOWING DETAILS IN ACCORDANCE WITH |
| | SEC. 213.1 FBC ACCESSIBILITY CODE. |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SEC. 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | LAVATORIES- SEC. 606.2. |
| | C) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SEC. 604.2. |
| | D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SEC. 604.4. |
| | E) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| | SURFACES FROM THE FINISHED FLOORS- SEC. 606.3. |
| | F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SEC. 603.3 |
| | G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | H) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS ? SEC. |
| | 604.6. |
| | I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| | 606.2. |
| | |
| | SHOWERS: |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | SHOWER- SEC. 608.2.2. PLEASE NOTE THAT THE LOCATION OF |
| | THE SHOWER, SHOWER CONTROLS, AND WATER CLOSET ARE NOT |
| | IN COMPLIANCE WITH SEC. 608.2.2.1 EXCEPTION: A LAVATORY |
| | COMPLYING WITH 606 SHALL BE PERMITTED ON ONE 30-INCH |
| | WIDE MINIMUM SIDE OF THE CLEARANCE PROVIDED THAT IT IS |
| | NOT ON THE SIDE OF THE CLEARANCE ADJACENT TO THE |
| | CONTROLS OR, WHERE PROVIDED, NOT ON THE SIDE OF THE |
| | CLEARANCE ADJACENT TO THE SHOWER SEAT. |
| | B) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS- SECS. 608.3.2, 609.4. |
| | C) LOCATION OF CONTROLS, FAUCETS, AND SHOWER SPRAYS- |
| | SEC. 608.5.2. |
| | D) SHOWER SPRAY UNIT SPECIFICATIONS PER SEC. 608.6. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |