| Plan Review Notes For Permit 22011026 |
| Permit Number |
22011026 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-02-14 12:05:04 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) PRODUCT SPECIFICATION HAVE BEEN PROVIDED; HOWEVER IT | | | IS STILL NOT CLEAR ON WHAT AND WHERE THE CARD READERS | | | WILL BE INSTALLED/LOCATED. | | | | | | PLEASE SHOW THE SPECIFIC LOCATION(S) OF THE CARD | | | READERS, INCLUDING ON WHAT SIDE OF THE DOOR OPENING. | | | | | | | | | 2) THERE IS NO ACKNOWLEDGEMENT OF COMPLYING WITH NFPA | | | 101, CH 7, MEANS OF EGRESS, IF APPLICABLE. | | | | | | PLEASE PROVIDE A NOTE OF ACKNOWEDGEMENT RO COMPLY. | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|