| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 16TH/ 2022 |
| | ACTION: DENIED |
| | |
| | 1) LIFE SAFETY SHEET: |
| | 1A) UNDER THE HEADING OF BUILDING CODE ANALYSIS THE |
| | OCCUPANT LOAD IS TAKEN USING A OCCUPANT LOAD FACTOR OF |
| | 100. IN THE 2020 FBC-BUILDING CODE TABLE 1004.5 THE |
| | OCCUPANT LOAD FACTOR IS TAKEN AT 150 SQ. FT. PLEASE |
| | UPDATE THE PLANS. |
| | |
| | 1B) THE LIFE SAFETY PLAN STATES THIS BUILDING IS IN A |
| | FIRE DISTRICT. PLEASE NOTE THERE HAS NOT BEEN ANY FIRE |
| | DISTRICTS SINCE THE 2001 FBC BUILDING CODE. |
| | |
| | 2) SHEET A-2 THE EXISTING DOOR LEADING INTO THE1 HOUR |
| | FIRE RATED VERTICAL EXIT IS NOT INCLUDED IN THE DOOR |
| | SCHEDULE, NO FIRE RATING GIVEN PER (FBC-BUILDING TABLE |
| | 716.5) NOR HARDWARE FOR THE EXIT. PLEASE READ, IN THE |
| | 2020 FBC-BUILDING CODE SECTION 1010.1.9.11 EXCEPTION 4, |
| | NOTE ON PLANS. |
| | |
| | 3A) SHEET ID-3 ELEVATIONS OF THE RESTROOM SHOW |
| | COMPLIANCE WITH 2020 FBC-B 1210.2.2. WALLS & |
| | PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING |
| | OFFICIAL INTERPRETATION ON 06/2020. IN BATHROOMS, |
| | RESTROOMS & SERVICE SINK AREAS EPOXY PAINT IS NO LONGER |
| | CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE. |
| | |
| | 3B) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF |
| | SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A |
| | SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT |
| | LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A |
| | TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |