| Plan Review Notes For Permit 22010971 |
| Permit Number |
22010971 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-27 10:44:45 | FIRE PROVISO COMMENTS: | | | 1) RELOCATED DROPS MAY NOT BE ABLE TO BE ISOLATED; | | | HOWEVER, THE FLOOR AREA MAY AND BE TESTED AT 200 PSI | | | FOR 2 HOURS. | | | IF COMMENT (1) IS NOT PERFORMED: | | | 2) TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13. | | | 3) USE OF FIRE PUMP TEST PRESSURE FOR WORKING PRESSURE | | | CALCULATIONS MINUS 5 PSI PER FLOOR FOR ELEVATION | | | PRESSURE LOSS. | | | |
|