| Plan Review Notes For Permit 22010966 |
| Permit Number |
22010966 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-04-19 14:59:56 | FIRE PROVISO: | | | | | | FIRE SPRINKLER: | | | | | | THE RETRACTABLE AWNING SYSTEM WILL | | | REQUIRE FULL FIRE SPRINKLER HEAD PROTECTION | | | PER NFPA 101 CH 12 & NFPA 13. | | | | | | FIRE ALARM: | | | | | | VISUAL & AUDIBLE NOTIFICATION DOES NOT APPEAR TO MEET | | | THE REQUIREMENTS OF NFPA 72 IN ALL AREAS. | | | | | | PLEASE ENSURE SHOP DRAWINGS REFLECT CODE COMPLIANCE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|