| 2022-02-08 16:06:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF AN ASSEMBLY OCCUPANCY ON A |
| | ROOF TOP OF A FIRE SPRINKLERED BUILDING THAT HAS |
| | ATTACHED ROOFING/CANOPIES FOR OCCUPANCY UNDER THEM. |
| | |
| | THE EXISTING FIRE SPRINKLER SYSTEM OF THE BUILDING IS |
| | REQUIRED TO BE EXTENDED INTO THE ATTACHED OCCUPIED |
| | SPACES. |
| | |
| | PER NFPA 101CHAPTER 12 |
| | |
| | 12.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 12.3.5.1 THE FOLLOWING ASSEMBLY OCCUPANCIES SHALL BE |
| | PROTECTED |
| | THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| | SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH 9.7.1.1(1): |
| | (1) DANCE HALLS |
| | (2) DISCOTHEQUES |
| | (3) NIGHTCLUBS |
| | (4) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING |
| | |
| | PLEASE REVIEW AND PROVIDE FOR FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | |
| | 2) THERE IS NO INDICATION OF FIRE ALARM PROTECTION. |
| | |
| | THERE IS AN EXISTING FIRE ALARM SYSTEM WITHIN THE |
| | BUILDING. |
| | |
| | ANY NOTIFICATION OF THE BUILDING FIRE ALARM SHALL BE |
| | EXTENDED FOR PROTECTION OF THIS NEW AREA. |
| | |
| | PER NFPA 101 CH 12 |
| | |
| | 12.3.4.1.2 ASSEMBLY OCCUPANCIES THAT ARE A PART OF A |
| | MULTIPLE OCCUPANCY |
| | PROTECTED AS A MIXED OCCUPANCY (SEE 6.1.14) SHALL BE |
| | PERMITTED TO BE |
| | SERVED BY A COMMON FIRE ALARM SYSTEM, PROVIDED THAT THE |
| | INDIVIDUAL |
| | REQUIREMENTS OF EACH OCCUPANCY ARE MET. |
| | |
| | |
| | 3) SHEET E 102 - THERE ARE INDICATIONS OF EXITS SIGNS |
| | HOWEVER, A REVIEW OF THE EXIT LOCATIONS REQUIRES |
| | MODIFICATION AND ADDITION. |
| | |
| | A) THE EXIT SIGN AT THE WEST END AT THE STAIRWAY DOES |
| | NOT APPEAR TO BE VISABLE FROM THE EAST END OF WALKWAY. |
| | IT APPEARS THAT IT CAN BE MORE VISABLE MOVED TO THE |
| | NORTH. |
| | |
| | B) THERE IS NO EXIT SIGN IN THE BAR AREA LEADING PEOPLE |
| | TO SOUTH STAIRWAY. |
| | |
| | C) THERE IS NO EXIT SIGN LEADING PEOPLE TO THE SOUTH |
| | STIRWAY FROM THE ROUNDED CORNER PRIVATE LOUNGE AREA. |
| | |
| | D) THE EXIT SIGN AT THE SOUTH STAIRWAY MAY NOT BE |
| | VISABLE FROM THE OPEN BAR AREA. |
| | |
| | |
| | |
| | 4) SHEETS ELECTRICAL - IT IS NOT CLEAR IF EMERGENCY |
| | LIGHTING IS PROVIDED THAT ILLUMINATES THE MEANS OF |
| | EGRESS. |
| | |
| | PER NFPA 12 |
| | |
| | 12.2.9 EMERGENCY LIGHTING. |
| | 12.2.9.1 EMERGENCY LIGHTING SHALL BE PROVIDED IN |
| | ACCORDANCE WITH SECTION |
| | 7.9. |
| | |
| | 7.9 EMERGENCY LIGHTING |
| | 7.9.1 GENERAL. |
| | 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF |
| | EGRESS SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE |
| | FOLLOWING: |
| | (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS |
| | 11 THROUGH 43 |
| | (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS |
| | ADDRESSED IN |
| | SECTION 11.7 |
| | (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS |
| | OF THIS CODE |
| | (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS |
| | (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF |
| | ENCLOSURES, FOR WHICH |
| | THE FOLLOWING ALSO APPLY: |
| | (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO |
| | INCLUDE A |
| | STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF |
| | ENCLOSURE |
| | MECHANICAL VENTILATION EQUIPMENT. |
| | (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED |
| | FOR THE |
| | STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER |
| | SUPPLY. |
| | (6) NEW SENSOR-RELEASE OF ELECTRICAL LOCKING SYSTEMS IN |
| | ACCORDANCE |
| | WITH 7.2.1.6.2 |
| | |
| | 7.9.1.2 FOR THE PURPOSES OF 7.9.1.1, EXIT ACCESS SHALL |
| | INCLUDE ONLY DESIGNATED |
| | STAIRS, AISLES, CORRIDORS, RAMPS, ESCALATORS, AND |
| | PASSAGEWAYS |
| | LEADING TO AN EXIT. FOR THE PURPOSES OF 7.9.1.1, EXIT |
| | DISCHARGE SHALL |
| | INCLUDE ONLY DESIGNATED STAIRS, RAMPS, AISLES, |
| | WALKWAYS, AND ESCALATORS |
| | LEADING TO A PUBLIC WAY. |
| | |
| | PLEASE PROVIDE DETAILS OF THE PRPOSED EMERGENCY |
| | LIGHTING MEETING THE REQUIREMENTS. |
| | |
| | |
| | |
| | 5) GENERAL INFOMATION - PLEASE PROVIDE DETAILS FOR ANY |
| | PROPOSED OPEN FLAME ORNAMENTAL LIGHTING AND/OR PROPANE |
| | HEATERS/PROPANE DECORATIVE LIGHTING. |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |