| 2022-03-09 09:03:20 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22010966 |
| | ADD: 185 BANYAN BLVD. |
| | CONT: MGM GENERAL CONTRACTING |
| | TEL: 954-532-9620 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MARCH 08TH/ 2022 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A0.01 ELISABETTAS GENERAL NOTES/ PROJECT DATA: |
| | |
| | 1A) THE AREA WHERE WORK IS TO BE COMPLETED IS ON THE |
| | ROOF TOP 3RD FLOOR. WHY IS THE FINISH FLOOR ELEVATION |
| | AT 8.93 NGVD ON THE 1ST FLOOR. PLEASE NOTE ALL |
| | ELEVATIONS ARE NOW IN NAVD88. |
| | |
| | 1B) THE PROJECT DATA STATES THE BUILDING IS FIRE |
| | SPRINKLERED. THE ROOF PLAN A2.06 THE EXISTING ROOF PLAN |
| | NOR DOES A0.03 NOT INDICATE FIRE SPRINKLERS IN |
| | ACCORDANCE WITH THE 2020 FBC-BUILDING CODE FOR THE |
| | EXISTING ELEMENTS SUCH AS THE FOYER OR RESTROOMS. THE |
| | NEW ELEMENTS SERVICE STATION 301 & BAR AREAS 309 & 310 |
| | ARE ALSO A NEW BUILDING ELEMENT THAT WOULD NEED TO SHOW |
| | COMPLIANCE WITH THE 2020 FBC-BUILDING CODE SECTION |
| | 903.2.11.3. |
| | |
| | 2) SHEET A0.03 ELISABETTAS LIFE SAFETY FLOOR PLAN: |
| | |
| | 2A) THE FLOOR PLAN INDICATES 145 SEATS ON THIS FLOOR |
| | AND ONLY ONE SEAT APPEARS TO BE DESIGNATED AS AN |
| | ACCESSIBLE SEAT LOCATED AT THE BAR. |
| | THE 2020 FBC-ACCESSIBILITY CODE SECTION 226.1 WHERE |
| | DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF |
| | FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES |
| | AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY |
| | WITH 902. 145 SEATS X 0.05 = 7.2 OR 8 ACCESSIBLE SEATS |
| | ARE REQUIRED. |
| | |
| | 2B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES |
| | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 2C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN |
| | RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL |
| | BE PROVIDED TO ALL DINING AREAS, BARS, INCLUDING RAISED |
| | OR SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS. |
| | |
| | 2D) 902.1. DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK |
| | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| | COUNTERS, AND WHERE COVERED BY THE ADA SCOPING |
| | PROVISIONS, EMPLOYEE WORKSTATIONS. |
| | |
| | 2E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 2E)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PLEASE REFER |
| | TO SHEET A2.02 FOR THE HEIGHT OF THE PORTION OF BAR |
| | THAT IS TO BE ACCESSIBLE IS INDICATED TO BE 36 INCHES |
| | HIGH. |
| | |
| | 2F) ON THE NORTH SIDE OF THE BUILDING THERE ARE 6 |
| | CABANAS IDENTIFIED AS CABANA 302 & CABANA 303. THERE |
| | ARE ONLY 2 EXTERIOR EXIT STAIRS AND THE VERTICAL |
| | CURTAINS BLOCK HE MEANS OF EGRESS TO GET TO THE |
| | NORTHWEST EXTERIOR STAIR. 2020 FBC-BUILDING CODE |
| | SECTION 1003.6 MEANS OF EGRESS CONTINUITY. OBSTRUCTIONS |
| | SHALL NOT BE PLACES IN THE MINIMUM WIDTH OR REQUIRED |
| | CAPACITY OF A MEANS OF EGRESS COMPONENT. THE MINIMUM |
| | WIDTH OR REQUIRED CAPACITY OF A MEANS OF EGRESS SHALL |
| | NOT BE DIMINISHED ALONG THE PATH OF EGRESS TRAVEL. |
| | DISCREPANCY IN PLANS LIFE SAFETY PLAN VERSES E-102 THE |
| | DEPTH OF THE CABANA AND THE REQUIRED EGRESS PATH. |
| | SHEET A2.06 ALSO SHOWS THE CABANA GOING ALL THE WAY TO |
| | THE GLASS HANDRAILS. |
| | |
| | 2G) 2020 FBC-BUILDING CODE, GUARDS SECTION 1015.3 |
| | EXCEPTION 4, SEE 1029.16.1 PERIMETER GUARDS. WHERE THE |
| | SEATBOARDS ARE ADJACENT TO THE PERIMETER, GUARD HEIGHT |
| | SHALL BE 42 INCHES MINIMUM, MEASURED FROM THE |
| | SEATBOARD. |
| | |
| | 3) SHEET A2.02: |
| | |
| | 3A) THE BAR PREP AREA NOTE 10 IS AT A HEIGHT OF 36 |
| | INCHES IN HEIGHT. |
| | 2020 ACCESS. SINKS. 2020 FBC-ACCESSIBILITY CODE SECTION |
| | 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED |
| | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| | SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 3B) THE WORK AREA BEHIND BAR AREA 309 DOES NOT PROVIDE |
| | THE WORKING HEIGHT OF THE LOWER COUNTER TOP NOR SINK |
| | HEIGHTS NOR COMPLIANCE WITH SINKS. 2020 |
| | FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 4) SHEET A3.03 NONE OF THE RESTROOM ELEVATION DETAILS |
| | PROVIDE CODE COMPLIANCE WITH THE 2020FBC-ACCESSIBILITY |
| | CODE: |
| | |
| | 4A) LAVATORIES 606.3. HEIGHT |
| | 4B) LAVATORIES 606.2 CLEAR FLOOR SPACE |
| | 4C) LAVATORIES 606.5 EXPOSED PIPES |
| | 4D) MIRRORS 603.3 MIRRORS LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. |
| | 4E) CLEARANCES AT WATER CLOSETS. 604.3 CLEARANCE |
| | 4F) GRAB BARS/ RESTROOMS 2020 FBC-ACCESSIBILITY CODE |
| | SECTION 609.4 HEIGHT TOP OF GRAB BAR NOT CENTER LINE. |
| | 4G) 2020 FBC-ACCESSIBILITY CODE SECTION 604.5.1 THE |
| | SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, |
| | LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL. |
| | 4H) 2020 FBC-ACCESSIBILITY CODE SECTION 604.5.2 REAR |
| | WALL. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE. |
| | 4I) TOILET PAPER DISPENSERS. 604.7. THE TOILET PAPER |
| | DISPENSER SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES |
| | MINIMUM TO 9 INCHES MAXIMUM IN FRONT OF THE WATER |
| | CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER. THE |
| | OUTLET OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND |
| | 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT |
| | BE LOCATED BEHIND THE GRAB BARS. |
| | |
| | 5) SHEET A3.02 RESTROOM INSWING DOOR. PLEASE REVIEW |
| | SECTION 603.2.3. DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE OR CLEARANCES REQUIRED FOR ANY FIXTURE. |
| | DOORS SHALL BE PERMITTED TO SWING INTO THE REQUIRED |
| | TURNING SPACE. PLEASE SEE EXCEPTION 2. WHERE TOILET |
| | ROOMS ARE FOR INDIVIDUAL USE AND A CLEAR FLOORS SPACE |
| | COMPLYING WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND |
| | THE ARC OF THE DOOR SWING. WHAT IS MISSING IS THE |
| | REQUIRED 30X48 INCH CLEAR FLOOR SPACE BEYOND THE ARC OF |
| | THE DOOR. USUALLY AT A 45% ANGLE TO THE DOOR ENTRANCE. |
| | |
| | 6) SHEET A5.03 THE CABINETRY FOR THE UNDER THE COUNTER |
| | REFRIGERATOR, COUNTERTOP AT 3 FEET 1 ? INCHES. |
| | DETAIL 3 BOTH THE UNDER THE COUNTER REFRIGERATOR |
| | CABINETRY AND STORAGE CABINETRY ARE BOTH 3FEET 1 ? |
| | INCHES IN HEIGHT. DETAIL 2 THE STORAGE CABINETRY IS |
| | LOWER AND WITHOUT A VERTICAL DIMENSION. 107.2.1. |
| | ADDITIONAL INFORMATION IS REQUIRED. DISCREPANCY IN |
| | PLANS. 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | |
| | 7) SHEET A6.02 WINDOW SCHEDULE WINDOW B DOES NOT |
| | INDICATE IF IT IS LARGE MISSILE IMPACT. 107.2.1. |
| | ADDITIONAL INFORMATION IS REQUIRED. WINDOWS 30 FEET OR |
| | LESS ABOVE GRADE REQUIRE LARGE MISSILE IMPACT GLAZING. |
| | 2020 FBC-B SECTION 1609.1.2.2. |
| | |
| | 8) SHEET 6-3 VERSES A0.01 PROJECT DATA: |
| | |
| | 8A) SHEET A0.01 PROJECT DATA LIST THE BUILDING TYPE AS |
| | A TYPE IIIA. DETAIL 2 INDICATES 6X20 GA. METAL STUDS, |
| | 5/8-INCH CDX PLYWOOD FOR WALLS, AND ROOF CDX PLYWOOD |
| | FOR THE DECK. PLEASE REVIEW THE REQUIREMENTS FOR |
| | EXTERIOR BEARING WALLS REQUIRING A 2-HOUR FIR RATING |
| | (TABLE 601) AND ROOF CONSTRUCTION (TABLE 601) 1 HOUR |
| | INCLUDING SECONDARY FRAMING MEMBERS. SECTION 602.3 FIRE |
| | RETARDANT TREATED WOOD. |
| | |
| | 8B)(1) ROOF OVER BAR FRAMING PLAN. THIS DETAIL |
| | INDICATES STEEL COLUMNS AND ROOF FRAMING LAYOUT. THERE |
| | IS NO INFORMATION AS TO HOW THE COLUMNS ARE GOING TO BE |
| | ONE-HOUR FIRE RESISTANCE RATING FOR THE PRIMARY |
| | STRUCTURAL FRAME PER 2020 FBC-BUILDING CODE TABLE 601 & |
| | SECTION 602.3. |
| | |
| | 8B)(2) ROOF OVER BAR FRAMING PLAN. THIS DETAIL |
| | INDICATES PRIMARY AND SECONDARY ROOF FRAMING MEMBERS AS |
| | WELL AS NOTE 1 ROOF DECK SHALL BE B DECK W/ 5/8-INCH |
| | DIA. PUDDLE WELD. THE PLAN IS SILENT AS TO COMPLIANCE |
| | WITH 1-HOUR FIRE RESISTANCE RATING REQUIREMENTS IN |
| | TABLE 601. |
| | |
| | 8C) PLEASE NOTE THIS IS A 3-STORY BUILDING AND 1ST |
| | OCCUPANCY FOR THE 3RD FLOOR. PLEASE PROVIDE HOW |
| | HORIZONTAL FIRE SEPARATION BETWEEN THE A2 ROOF TOP |
| | OCCUPANCY AND 2ND FLOOR BUSINESS IS TO OCCUR FOR MIXED |
| | OCCUPANCIES 2020 FBC-B TABLE 707.3.10 FOR ASSEMBLY VS. |
| | BUSINESS OCCUPANCIES, 2 HOURS AND COLUMNS SUPPORTING |
| | THE 2ND FLOOR. |
| | |
| | 8D) DETAIL # 6 CANOPY COLUMNS FIELD WIELDING AND SHEET |
| | S-4 DETAILS 1 & 2. WELDED OR BOLTED CONNECTIONS. THIS |
| | BUILDING CONTAINS EITHER BOLTED AND OR WELDED |
| | CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD |
| | PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666 OR ACTING CHIEF BUILDING INSPECTOR |
| | RICHARD BRUNELLE AT 561-805-6670. |
| | |
| | 9) SHEET S-0 PROVIDES THE WIND DESIGN CRITERIA BUT DOES |
| | NOT PROVIDE THE PRESSURES FOR ROOF ZONES, 1, 2,OR 3 & |
| | WALL ZONES 4 & 5 FOR COMPONENTS AND CLADDING. PLEASE |
| | ALSO INCLUDE THE MEAN ROOF HEIGHT. PLEASE PROVIDE ALL |
| | COMPONENT AND CLADDING PRESSURES IN VASD. THANK YOU, |
| | ALL PRODUCT APPROVALS ARE IN VASD. |
| | |
| | 10) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS |
| | AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS |
| | (B) WINDOWS & MULLIONS |
| | (C) WALL LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP VENTILATORS |
| | |
| | 11) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 12) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 13) IDENTIFY GLAZING. PLEASE IDENTIFY IN THE PRODUCT |
| | APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL |
| | PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING |
| | WIDTH & HEIGHT, SILL HEIGTH, TYPE OF GLAZING, MULLION |
| | SIZE, LENGTH IF UNREINFORCED OR REINFORCED INFORMATION |
| | IF REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR |
| | EACH OPENING SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. |
| | WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH |
| | APPROVED MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND |
| | SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| | SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| | USED IN THE TESTS. |
| | |
| | 14) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 15) SHEET A5.04 DETAILS 3 & 5 BOTH SHOW THE USE OF ? |
| | INCH CDX PLYWOOD, PLEASE REVIEW SECTION 602.3 EXTERIOR |
| | WALLS ARE OF NONCOMBUSTIBLE MATERIAL. |
| | |
| | 16) SHEET A5.04 DETAILS 3 & 5 BOTH SHOW THE USE OF ? |
| | INCH CDX PLYWOOD AS ROOF SHEATHING WHEREAS S-3 SHOWS ON |
| | THE ROOF FRAMING OVER THE BAR NOTE 1 1 ? INCH 20-GAUGE |
| | B DECKING, DISCREPANCY IN PLANS. |
| | 107.2.1. ADDITIONAL INFORMATION IS REQUIRED. 2020 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION. |
| | |
| | 17) SHEET A5.04 DETAILS 3 BAR ROOF DETAIL SHOW THE USE |
| | OF ? INCH CDX PLYWOOD ON THE EXTERIOR ROOF TOP WALL AS |
| | WELL AS A SUB-CEILING DECKING MEMBER. TYPE IIIA |
| | CONSTRUCTION. SEE SECTION 603 FOR TYPE III |
| | CONSTRUCTION. THE OTHER ISSUE IS THE ROOF FRAMING |
| | MEMBERS ARE STATED TO BE BAR JOIST IN THE STRUCTURAL |
| | PLANS, HOW WILL ANY CEILING SUB-SHEATHING BE ATTACHED |
| | TO THE BAR JOIST? 107.2.1. ADDITIONAL INFORMATION IS |
| | REQUIRED. 2020 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION. |
| | |
| | 18) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |