| 2022-03-23 14:28:27 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PREFABRICATED GENERATOR PADS ARE REQUIRED TO HAVE A | | | PRODUCT APPROVAL OR SIGNED AND SEALED SITE SPECIFIC | | | ENGINEERING. FBC AMENDMENTS 107.2.1 | | | | | | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE | | | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE | | | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 | | | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | | PARKING LOTS AND LOADING DOCKS. | | | | | | | | | | | | |
|