| Plan Review Notes For Permit 22010944 |
| Permit Number |
22010944 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-07-15 11:02:15 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NOT RESOLVED. SUBMIT THE WIND DESIGN ENGINEERING FOR | | | THE PREFABRICATED GENERATOR PAD. THE ENGINEER IS | | | REQUIRED TO DIGITALLY SIGN AND SEAL THE PREFAB PAD | | | DOCUMENTS. [PREFABRICATED GENERATOR PADS ARE REQUIRED | | | TO HAVE A PRODUCT APPROVAL OR SITE SPECIFIC | | | ENGINEERING. FBC AMENDMENTS 107.2.1] | | | | | | 2) NOT RESOLVED. THE NOTE ON THE SURVEY STILL HAS 5 | | | FEET FROM OPENINGS. [THE GENERATOR EXHAUST IS REQUIRED | | | TO BE AT LEAST 10 FEET FROM ANY OPENINGS INTO A | | | BUILDING. R303.5.1 INTAKE OPENINGS. MECHANICAL AND | | | GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED | | | NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR | | | NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING | | | VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING | | | DOCKS.] | | | |
|