Plan Review Notes
Plan Review Notes For Permit 22010944
Permit Number 22010944
Review Stop B
Sequence Number 2
Notes
Date Text
2022-07-15 11:02:15PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT RESOLVED. SUBMIT THE WIND DESIGN ENGINEERING FOR
 THE PREFABRICATED GENERATOR PAD. THE ENGINEER IS
 REQUIRED TO DIGITALLY SIGN AND SEAL THE PREFAB PAD
 DOCUMENTS. [PREFABRICATED GENERATOR PADS ARE REQUIRED
 TO HAVE A PRODUCT APPROVAL OR SITE SPECIFIC
 ENGINEERING. FBC AMENDMENTS 107.2.1]
  
 2) NOT RESOLVED. THE NOTE ON THE SURVEY STILL HAS 5
 FEET FROM OPENINGS. [THE GENERATOR EXHAUST IS REQUIRED
 TO BE AT LEAST 10 FEET FROM ANY OPENINGS INTO A
 BUILDING. R303.5.1 INTAKE OPENINGS. MECHANICAL AND
 GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED
 NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR
 NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING
 VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING
 DOCKS.]
  