| Plan Review Notes For Permit 22010944 |
| Permit Number |
22010944 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-14 11:29:40 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | RISER DIAGRAM DOES NOT SHOW ALL WIRE SIZE, FROM METER | | | TO FIRST TRANSFER SWITCH. 215.5 | | | | | | FROM TRANSFER SWITCH TO 200A PANEL #3??? #3 NOT LARGE | | | ENOUGH. 310.15(B)(7)(1,2) | | | | | | NO WIRE SIZES FROM 200A PANEL TO 200A PANEL. 215.5 | | | | | | PLAN NOT SIGNED. PLAN IS REQUIRED TO BE SIGNED AND | | | SEALED BY THE ELECTRICAL CONTRACTOR QUALIFIER. FS | | | 471.003(2)(H); 471.025; FBC 107.2.1 | | | | | | |
|