 RISER DIAGRAM DOES NOT SHOW ALL WIRE SIZE, FROM METER
 TO FIRST TRANSFER SWITCH. 215.5
  
 FROM TRANSFER SWITCH TO 200A PANEL #3??? #3 NOT LARGE
 ENOUGH. 310.15(B)(7)(1,2)
  
 NO WIRE SIZES FROM 200A PANEL TO 200A PANEL. 215.5
  
 PLAN NOT SIGNED. PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
  
  