| 2022-05-02 11:05:13 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | 3.) FBC B 107, THE PLAN AND APPLICATION REFER TO |
| | WINDOWS IN SEVERAL AREAS. NO PRODUCT APPROVAL FOR |
| | WINDOWS WAS SUBMITTED AND THERE IS NOTHING ON THE |
| | OPENING SCHEDULE FOR WINDOWS. IF WINDOWS ARE NOT |
| | PROPOSED, SUBMIT A NEW APPLICATION AND PLAN REMOVING |
| | WINDOWS FROM SCOPE OF WORK. |
| | |
| | 4.) FBC B 107, ALL PLAN SHEETS NEED TO BE SIGNED BY THE |
| | PERSON TAKING RESPONSIBILITY FOR THE PLAN SHEETS. IF |
| | THE PLAN SHEETS ARE FROM SIW WINDOWS & DOORS, AS TITLE |
| | BLOCK INDICATES, THEN THE PRINTED NAME & SIGNATURE |
| | (INCLUDING SEAL IF ARCHITECT OR ENGINEER IS SIGNING) |
| | MUST BE ON EACH PLAN SHEET. IF THERE IS NOT A TITLE |
| | BLOCK ON PLANS, THEN IT WILL BE CONSIDERED DESIGNED BY |
| | THE INDIVIDUAL THAT PRINTS NAME AND SIGNS NAME, SUCH AS |
| | A GENERAL CONTRACTOR. |
| | THE (3) PLAN SHEETS NEED TO BE NUMBERED AS A SET OF (3) |
| | AS FOLLOWS: |
| | |
| | PLAN SHEET (LAYOUT-SCHEDULE-ELEVATION) SHOULD BE |
| | LABELED 1 OF 3 NOT 1 OF 1. |
| | PLAN SHEET (DOOR LAYOUT) SHOULD BE LABELED 2 OF 3 NOT 1 |
| | OF 1. |
| | PLAN SHEET (DOOR LAYOUT/OCCUPANCY INFORMATION) SHOULD |
| | BE LABELED AS IS 3 OF 3. |