| 2022-04-07 13:05:02 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22010929 319 CLEMATIS ST |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1. NEW COMMENT: I-4002/DETAIL 6; PER FBC ACC 606.3, |
| | LAVATORY SHALL BE INSTALLED WITH THE RIM 34 INCHES |
| | ABOVE THE FINISH FLOOR. |
| | |
| | 2. NEW COMMENT: P-2001, P-4001, P-5001 AND P-6001 |
| | (PLUMBING FIXTURE SCHEDULE) DO NOT ADDRESS ADDED MOP |
| | SINK. PER WPB FBC 107.2.1, REVISE AND RESUBMIT. |
| | |
| | 3. NEW COMMENT: P-2004/SECOND FLOOR SANITARY RISER; PER |
| | FBC PL 914.2, THE CIRCUIT VENT CONNECTION SHALL BE |
| | LOCATED BETWEEN THE TWO MOST UPSTREAM FIXTURE DRAINS. |
| | THE VENT SHALL CONNECT TO THE HORIZONTAL BRANCH AND |
| | SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 905. THE |
| | CIRCUIT VENT PIPE SHALL NOT RECEIVE THE DISCHARGE OF |
| | ANY SOIL OR WASTE. |
| | |
| | 4. REQUEST FOR SLAB REPAIR DETAIL PARTIALLY COMPLIED; |
| | SEE P-6001/DETAIL 4. PER WPB FBC 107.2.1, ADD NOTE "A |
| | COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE FOR |
| | FINAL INSPECTION." |
| | |
| | |
| | END OF COMMENTS |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |