Plan Review Notes
Plan Review Notes For Permit 22010929
Permit Number 22010929
Review Stop P
Sequence Number 2
Notes
Date Text
2022-04-07 13:05:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22010929 319 CLEMATIS ST
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. NEW COMMENT: I-4002/DETAIL 6; PER FBC ACC 606.3,
 LAVATORY SHALL BE INSTALLED WITH THE RIM 34 INCHES
 ABOVE THE FINISH FLOOR.
  
 2. NEW COMMENT: P-2001, P-4001, P-5001 AND P-6001
 (PLUMBING FIXTURE SCHEDULE) DO NOT ADDRESS ADDED MOP
 SINK. PER WPB FBC 107.2.1, REVISE AND RESUBMIT.
  
 3. NEW COMMENT: P-2004/SECOND FLOOR SANITARY RISER; PER
 FBC PL 914.2, THE CIRCUIT VENT CONNECTION SHALL BE
 LOCATED BETWEEN THE TWO MOST UPSTREAM FIXTURE DRAINS.
 THE VENT SHALL CONNECT TO THE HORIZONTAL BRANCH AND
 SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 905. THE
 CIRCUIT VENT PIPE SHALL NOT RECEIVE THE DISCHARGE OF
 ANY SOIL OR WASTE.
  
 4. REQUEST FOR SLAB REPAIR DETAIL PARTIALLY COMPLIED;
 SEE P-6001/DETAIL 4. PER WPB FBC 107.2.1, ADD NOTE "A
 COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE FOR
 FINAL INSPECTION."
  
  
 END OF COMMENTS
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 22010929 319 CLEMATIS ST
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved