Plan Review Notes
Plan Review Notes For Permit 22010929
Permit Number 22010929
Review Stop P
Sequence Number 1
Notes
Date Text
2022-02-24 12:15:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22010929 319 CLEMATIS ST
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. G-0003, G-0004 AND G-0005; 2010 ADA REGULATIONS.
 MOST OF THE REQUIREMENTS OF 2020 FLORIDA BUILDING CODE
 FOR PLUMBING FIXTURES ARE MET ON THESE PAGES; SOME ARE
 ADDRESSED ON I-4002, I-4003, I-4004, I-4005, I-4006,
 I-4007, I-4016 AND I-4017 AND MY COMMENTS BELOW ARE
 DIRECTED AT THOSE SHEETS AS THE ADA SHEETS DID NOT
 ADDRESS THEM.
 ...A) PER WPB FBC 107.2.1, PROVIDE NOTE ON ALL SHEETS
 LISTED ABOVE STATING "COMPLY WITH 2020 FLORIDA BUILDING
 CODE, ACCESSIBILITY, 7TH EDITION"
 ...B) ) PER WPB FBC 107.2.1, PROVIDE NOTE ON SHEETS
 I-4002, I-4003, I-4004, I-4005, I-4006, I-4007, I-4016
 AND I-4017 STATING "REFER TO G-0003, G-0004 AND G-0005
 FOR ADDITIONAL ACCESSIBILITY REQUIREMENTS."
  
 2. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOMS AND ACCESSIBLE PLUMBING FIXTURES
 INDICATING THE FOLLOWING:
 ...A) I-4004: PROVIDE TURNING SPACE FOR TRANSFER SHOWER
 VESTIBULES (FBC ACC 304.3.1 OR 304.3.2) AND GRAB BAR
 HEIGHTS FOR TRANSFER SHOWERS (FBC ACC 609.4).
 ...B) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES
 MAXIMUM MEASURED TO THE TOP OF THE SEAT PER FBC ACC
 604.4.
 ...C) I-4002, I-2003, I-4016 AND I-4017: PROVIDE THE
 KNEE AND TOE CLEARANCES (DIMENSIONS)FOR THE LAVATORIES.
 SEE FBC ACC 606.2.
 ...D) I-4002, I-2003, I-4016 AND I-4017: PROVIDE ON THE
 ELEVATION DETAIL OF THE LAVATORIES IN THE WHEELCHAIR
 ACCESSIBLE TOILET COMPARTMENT THE HEIGHTS OF THE SINK
 RIMS FROM THE FINISHED FLOORS PER FBC 602.3. AND THE
 KNEE AND TOE CLEARANCES- SECS 606.2 & 606.3 FBC ACC. A
 ...E) I-4002, I-2003, I-4016 AND I-4017: MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND PER FBC ACC 603.3. PER WPB FBC 107.2.1
 INDICATE REFLECTING SURFACE.
 ...F) I-4002 AND I-4007: PROVIDE CLEAR FLOOR OR GROUND
 SPACE FOR PANTRY SINK AND DRINKING FOUNTAIN. COMPLYING
 WITH FBC ACC 305.
  
 3. DRINKING FOUNTAIN: PROTRUDING OBJECTS 307.2
 PROTRUSION LIMITS 307.2. OBJECTS WITH LEADING EDGES
 MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE
 THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES
 HORIZONTALLY INTO THE CIRCULATION PATH.
  
 4. DRINKING FOUNTAINS SHALL COMPLY WITH FBC ACC 306,
 307 AND 602 PER FBC ACC 602.1. PER WPB FBC 107.2.1,
 PROVIDE DETAIL SHOWING THE FOLLOWING:
 ...A) SPOUT OUTLETS SHALL BE 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND PER FBC ACC 602.4.
 ...B) SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES MINIMUM AND 43 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC
 602.7.
 ...C) DIMENSIONED KNEE AND TOE SPACE PER FBC ACC 306,
 307.
  
 5. PLAN SHEET G-0003/PLUMBING CALCULATIONS: PER FBC PL
 TABLE 403.1, A SERVICE SINK IS REQUIRED; EITHER MAKE
 PROVISION FOR AND PROVIDE, OR IF EXISTING OUTSIDE OF
 SCOPE, NOTE THE SAME.
  
 6. PER WPB FBC 107.2.1, PROVIDE NOTE OR CHART OF
 REQUIRED MINIMUM SLOPES OF SANITARY DRAIN PIPING
 SHOWING COMPLIANCE WITH FBC PL 704.1/TABLE 704.1.
  
 7. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 8. PER FBC PL 604.9 A WATER HAMMER ARRESTOR IS REQUIRED
 FOR THE COLD WATER TO THE REFRIGERATOR
  
 9. PER WPB FBC 107.2.1, SPECIFY CARRIER FOR WALL HUNG
 WATER CLOSETS SHOWING COMPLIANCE WITH FBC PL 405.4.3.
  
 10. PLAN SHEET E3.1/PANEL 3A INDICATES A COFFEE MACHINE
 AND A CAPPUCCINO MACHINE. IF WATER CONNECTIONS ARE
 REQUIRED FOR THESE ITEMS, PER WPB FBC 107.2.1, SHOW ON
 DRAWINGS; ADD TO CONNECTION SCHEDULE AND SPECIFY AND
 PER FBC PL 608.1.2, SPECIFY AND PROVIDE LEAD FREE
 BACKFLOW PREVENTERS.
  
 11. P-6001/PLUMBING FIXTURE SCHEDULE INDICATES EZH20
 BI-LEVEL DRINKING FOUNTAIN WITH BOTTLE FILLER.
 I-6006/PLUMBING SCHEDULE CALLS EZWS-EDFPBM117K WITH
 BI-LEVEL DRINKING FOUNTAIN WITH BOTTLE FILLER. PER WPB
 FBC 107.2.1, CLARIFY AND RECONCILE THE TWO DRAWINGS.
  
 12. P-6001/PLUMBING FIXTURE SCHEDULE INDICATES SLOAN
 ST-2469 WALL HUNG WATER CLOSET WITH REAR SPUD INLET AND
 SLOAN CX8158-1.28 CONCEALED FLUSHOMETER.
 I-6006/PLUMBING SCHEDULE CALLS FOR THE SAME WATER
 CLOSET WITH A MAC FAUCETS ATV-2 EXPOSED FLUSHOMETER FOR
 A TOP INLET. PER WPB FBC 107.2.1, CLARIFY AND RECONCILE
 THE TWO DRAWINGS.
  
 13. P-6001/PLUMBING FIXTURE SCHEDULE INDICATES SLOAN
 SU-7019 WALL HUNG URINAL WITH REAR SPUD INLET AND SLOAN
 CX8198-0.5 CONCEALED FLUSHOMETER. I-6006/PLUMBING
 SCHEDULE CALLS FOR THE URINAL WITH A MAC FAUCETS AUV-2
 EXPOSED FLUSHOMETER WITH A TOP INLET. PER WPB FBC
 107.2.1, CLARIFY AND RECONCILE THE TWO DRAWINGS.
  
 14. I-4002, I-2003, I-4016 AND I-4017 ALL INDICATE
 EXPOSED FLUSHOMETERS FOR WATER CLOSETS AND URINALS.
 I-6006/PLUMBING SCHEDULE CALLS FOR EXPOSED
 FLUSHOMETERS; P-6001/PLUMBING FIXTURE SCHEDULE CALLS
 FOR CONCEALED FLUSHOMETERS. PER WPB FBC 107.2.1,
 CLARIFY AND RECONCILE ALL DRAWINGS.
  
 15. P-6001/EWH MOUNTING AND PIPING DETAIL:
 ...A) PROVIDE VACUUM BREAKER FOR HOSE BIB PER FBC PL
 608.16.4.2.
 ...B) PROVIDE WATER HAMMER ARRESTOR AT SOLENOID VALVE
 PER FBC PL 604.9.
 ...C) PAN DRAIN DISCHARGES TO FFD-1. PER WPB FBC
 107.2.1, PROVIDE TRAPPED AND VENTED FFD-1 AND
 APPROPRIATE TRAP SEAL PROTECTION AS REQUIRED BY FBC PL
 1002.4.1
  
 16. P-6001/DETAIL3 INDICATES A DISHWASHER. PER WPB FBC
 107.2.1, INDICATE ON PLANS AND PROVIDE A WATER HAMMER
 ARRESTOR ON HOT WATER SUPPLY. IF THE DETAIL IS NOT
 APPLICABLE, PER WPB FBC 107.2.1, REMOVE IT.
  
 17. PER WPB FBC 107.2.1, PROVIDE A DESCRIPTION OF EI-1,
 ADD TO PLUMBING FIXTURE SCHEDULE/CONNECTION SCHEDULE.
 PROVIDE WATER HAMMER ARRESTOR IF APPLICABLE; SEE FBC PL
 604.9. FBC PL 608.1.2, SPECIFY PROVIDE LEAD FREE
 BACKFLOW PREVENTER IF APPLICABLE; SEE FBC PL 608.1
  
 18. IS LEVEL 1 ELEVATED OR SLAB ON GRADE? IF SLAB ON
 GRADE, PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR
 DETAIL ON THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE
 MINIMUM THICKNESS AND PSI OF THE CONCRETE TO BE
 REPLACED. SHOW SIZE, LENGTH, SPACING (ON CENTER),
 MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE MATERIAL FOR
 DOWELS. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT
 OF THE SOIL AS WELL AS THE REQUIRED VAPOR BARRIER OVER
 WELL COMPACTED SOIL. A COPY OF THE TERMITE CERTIFICATE
 SHALL BE ONSITE FOR FINAL INSPECTION.
  
 19. PER WPB FBC 107.2.1, PROVIDE APPLICABLE RATED
 WALL/FLOOR DETAILS FOR PLUMBING PENETRATIONS COMPLYING
 WITH THE REQUIREMENTS OF FBC CHAPTER 7.
  
 20. P-6001/DETAIL 5: PER FBC PL 602.2 SHUTOFF VALVES
 SHALL BE LOCATED ON THE FIXTURE SUPPLY TO EACH PLUMBING
 FIXTURE. THE DETAIL PROVIDED IS ADEQUATE WHEN ONLY ONE
 FIXTURE IS INVOLVED. HOWEVER, THE PLANS INDICATE
 INSTANCES WHERE MULTIPLE FIXTURES ARE SERVED BY THE
 SAME WATER HEATER. PER WPB FBC 107.2.1, ADD NOTE TO
 DETAIL STATING THAT WHERE MORE THAN ONE FIXTURE IS
 SERVED BY THE WATER HEATER, EACH FIXTURE SHALL HAVE A
 DEDICATED SHUTOFF VALVE.
  
 21. P-6001/PLUMBING FIXTURE SCHEDULE: PER WPB FBC
 107.2.1, ADD PANTRY SINK TO SCHEDULE.
  
 22. P-5001/WATER RISER FOR OFFICE TOILET ROOMS AND
 PANTRY SINK: PER WPB FBC 107.2.1, PLEASE CLEARLY
 INDICATE THE SIZES OF THE COLD WATER DISTRIBUTION FROM
 THE 2 INCH REDUCING TEE THAT SERVES THE PANTRY AND THE
 WATER CLOSETS TO THE WATER CLOSETS. IF NECESSARY,
 REMOVE THE WATER HEATER FOR CLARITY.
  
 23. GENERAL NOTE; SHOULD ANY BACKFLOW PREVENTERS BE
 REQUIRED, PER WPB FBC 107.2.1, A SCHEDULE SHALL BE
 PROVIDED LISTING FIXTURE OR EQUIPMENT CONNECTED, TYPE
 OF DEVICE AND APPLICABLE STANDARD (SEE FBC PL TABLE
 608.1) AND NOTE STATING DEVICES SHALL BE LEAD FREE.
  
 END OF COMMENTS
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 22010929 319 CLEMATIS ST
  