Plan Review Notes
Plan Review Notes For Permit 22010929
Permit Number 22010929
Review Stop B
Sequence Number 1
Notes
Date Text
2022-03-16 10:40:30REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ACCESSIBLE RESTROOM - PLEASE USE THE TERM
 "REFLECTIVE SURFACE" WHEN REFERRERING TO THE BOTTOM OF
 THE MIRROR DIMENSION FROM THE FLOOR PER FBC A 603.3
 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 2) ACCESSIBLE RESTROOM - THERE SHOULD BE 12 INCHES
 CLEARANCE FROM THE GRAB BARS AND ITEMS ABOVE SUCH AS
 (TA-08) SHOWN ON DRAWING I-4003 DETAIL NUMBER 5 - FBC A
 609.3 SPACING. THE SPACE BETWEEN THE GRAB BAR AND
 PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES (305 MM)
 MINIMUM.
  