2022-03-03 14:54:261ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22010926
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-3001 INDICATES AN EF-1 AND AN EF-2. SHEET
 M-4001: THE FAN SCHEDULE DOES NOT SHOW AN EF-2, PLEASE
 PROVIDE INFORMATION ON EF-2. FBC 107.2.1
  
 2) SHEET M-4001 INDICATES AN AHU-1-3 BUT THIS UNIT IS
 NOT SHOWING ON THE FLOOR PLANS. PLEASE PROVIDE A
 DRAWING SHOWING THIS UNIT?S LOCATION ON THIS PROJECT.
 FBC 107.2.1
  
 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE ACCORDING TO FBC M 403.3.1.1 AND TABLE
 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  