| Plan Review Notes For Permit 22010921 |
| Permit Number |
22010921 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-07 14:01:54 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OF CLOSELY SPACED SIDEWALL | | | SPRINKLERS ALONG EACH SIDE OF THE COMMON AREA. | | | | | | MY UNDERSTANDING WAS THAT THIS CONFIGURATION WAS A | | | TEMPORAY INSTALLATION FOR CONSTRUCTION PURPOSES. | | | | | | IF YOU ARE PROPOSING TO KEEP THIS AS A PERRMANENT | | | INSTALLATION PLEASE PROVIDE THE CODE SECTION WITHIN | | | NFPA 13 THAT ALLOWS FOR IT. | | | | | | | | | 1A) THERE ARE INDICATIONS OF DROPS ALONG THE OUTSIDE | | | WALLS OF THE ENTIRE FLOOR THAT APPEAR TO SPACED TOO FAR | | | APART AND DO NOT COVER POTENTIAL VOID SPACES. | | | | | | PLEASE PROVIDE A REVIEW OF THESE AREAS INDICATING THE | | | AREAS AND DEPTHS OF VOIDS SHOWING COMPLIANCE WITH THE | | | SECTION OF NFPA 13 . | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|