| 2022-06-10 15:35:43 | FAILED |
| | |
| | 1) THE CITYPLACE RETAIL MANAGEMENT APPROVAL STAMP IS |
| | REQUIRED ON THE PLANS. ALTERNATIVELY, YOU MAY PROVIDE A |
| | LETTER FROM CITYPLACE RETAIL MANAGEMENT WHICH APPROVES |
| | THE SPECIFIC PLANS SUBMITTED AS PART OF THE PERMIT. |
| | |
| | 2) THIS PERMIT WILL NOT BE APPROVED BY ZONING UNTIL THE |
| | SUBMITTED MINOR PLANNED DEVELOPMENT AMENDMENT IS |
| | APPROVED. THE COMMENTS BELOW ARE INCLUDED WITH THE |
| | MINOR PLANNED DEVELOPMENT AMENDMENT REVIEW. |
| | |
| | 3) THE CITYPLACE DEVELOPMENT OF REGIONAL IMPACT, WHICH |
| | INCLUDES ROSEMARY SQUARE, REQUIRES THAT MECHANICAL |
| | EQUIPMENT, TO INCLUDE TRANSFORMERS, IS SCREENED FROM |
| | PUBLIC VIEW. THE NORTH SIDE OF THE TRANSFORMERS AND |
| | CONVERSION CABINETS MUST BE SCREENED FROM THE SIDEWALK. |
| | STAFF WILL NOT APPROVE THE PROJECT WITH UNSCREENED |
| | MECHANICAL EQUIPMENT ADJACENT TO THE SIDEWALK. NOTE: |
| | THE TRANSFORMERS WILL NEED TO BE ORIENTED SO THAT THE |
| | EQUIPMENT CLEAR SPACE ORIENTS TO PARALLEL TO THE |
| | SIDEWALK. |
| | |
| | 4) THE PARKING SPACE STRIPING MUST CONFORM TO CITY |
| | STANDARDS, WHICH REQUIRE WHITE, NOT GREEN STRIPES. THE |
| | ELECTRIC VEHICLE NOTE MAY BE IN GREEN. |
| | |
| | 5) THE DIMENSION FOR THE DOUBLE STRIPING SHOWN ON SHEET |
| | C-201 IS INCORRECT. THE FULL WIDTH OF THE DOUBLE |
| | STRIPING IS 20 INCHES (4" + 12" + 4"), NOT 21 INCHES. |
| | |
| | 6) THE ADA ACCESS AISLE IS REQUIRED TO BE WHITE |
| | REGARDLESS OF THE SURFACE ON WHICH IT IS PAINTED. |
| | |
| | 7) THE CLUSIA ROSEA IS NOT PERMITTED TO BE USED AT THIS |
| | LOCATION. YOU WILL NEED TO USE EITHER SCHEFFLERA |
| | ARBORICOLA GREEN OR PODACRPUS AS BOTH ARE EASIER TO |
| | MAINTAIN AND CURRENTLY EXIST IN THE PLANTING AREA. |
| | |
| | 8) PROVIDE THE OVERALL HEIGHT OF THE METER PANEL H |
| | FRAME STRUCTURE. THE FULL HEIGHT WILL NEED TO BE |
| | SCREENED BY THE LANDSCAPE. |
| | |