2022-05-16 10:37:06ELECTRIC REVIEW FAILED
 1) 300MCM CONDUCTORS FEEDING NBDC180 DISPENSERS MAXIMUM
 ALLOWABLE OVERCURRENT PROTECTION IS 300-AMPS. PLEASE
 DETAIL CONDUCTORS WITH SUFFICIENT AMPACITY FEEDING
 NBDC180 DISPENSERS THAT ALLOW FOR 350 AMP OVERCURRENT
 PROTECTION OR REDUCE OVERCURRENT PROTECTION SIZE TO 300
 AMP.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  