| Plan Review Notes For Permit 22010919 |
| Permit Number |
22010919 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-26 10:55:44 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS NO CLEAR INDICATION OF THE LOCATION OF THE | | | EMERGENCY DISCONNECT THAT CAN BE | | | USED BY EMERGENCY PERSONNEL IN THE EVENT OF A FIRE OR | | | OTHER INCIDENT WHERE THE POWER TO THE | | | EV SYSTEM CAN BE DEENERGIZED. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC | | | LOCATION OF THE EMERGENCY POWER DISCONNECT | | | AND APPLICABLE SIGNAGE FOR QUICK & EASY IDENTIFICATION | | | OF ARRIVING EMERGENCY PERSONNEL. | | | | | | IF NEEDED, PLEASE CONTACT MY OFFICE TO DISCUSS PROPOSED | | | LOCATIONS PRIOR TO RESUBMITTAL. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|