| 2022-02-07 20:25:19 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | |
| | 2.PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE |
| | MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| | AVAILABLE PER NEC 110.24. |
| | |
| | 3. VALUE LOW FOR AMOUNT OF WORK SHOWN. PROVIDE COST |
| | BREAKDOWN. FBC 109.3 |
| | |
| | 4. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF ALL |
| | MATERIALS AND EQUIPMENT. (CAR CHARGERS, CABINETS, ETC) |
| | NEC 110.2 110.3B |
| | |
| | 5. NO DISCONNECTS SHOWN WITHIN SIGHT OF CAR CHARGERS |
| | NEC 625.43 |
| | |
| | 6. ON SHEET E-200 (FEEDER SCHEDULE NOTE #5) PROVIDE |
| | CONDUIT FILL CALCULATION OF CIRCULAR MILS FOR PROPOSED |
| | CONDUCTORS (ALL IN HALF INCH CONDUIT). ALSO ARE THESE |
| | CLASS 2 CONDUCTORS OR LINE VOLTAGE? HIGH AND LOW |
| | VOLTAGE CANNOT BE MIXED IN SAME CONDUIT. NEC 725.136B |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |