Plan Review Notes
Plan Review Notes For Permit 22010918
Permit Number 22010918
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-02-07 11:45:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF A FLOOR PLAN SHOWING THE
 EXACT LOCATION OF THE PROPOSED.
  
 PLEASE PROVIDE A FLOOR PLAN WITH SPECIFIC DETAILS.
  
  
 1A) THERE IS NO INDICATION OF PROVIDE FOR FIRE
 SPRINKLER PROTECTION WITHIN THE COOLERS.
  
 FIRE PROTECTION IS REQUIRED TO BE EXTENDED TO WITHIN
 THE COOLERS.
  
 ANY WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLVE NOTE OF
 ACKNOWLEDGEMENT TO PROVIDE PROTECTION.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  